background image

Danaher Motion Superior Electric

SS2000MD4

15

400030-043 Rev G

4.5 C

URRENT

S

ETTINGS

The proper current setting for each motor is shown on the individual torque vs. speed
curves. Use this current level to obtain the torque shown. Switches 1 through 7 select the
current level. Select the desired operating current by setting the appropriate switch to
position 1 (ON). The OFF position is labeled "0". Only one switch should be ON. If two
or more switches are ON, the one that selects the highest current level is the active
switch. The switch settings are:

Position

Current

(amperes)

None

0.5

1

0.75

2

1.0

3

1.5

4

2.0

5

2.5

6

3.0

7

3.5

4.6 S

TEP

R

ESOLUTION

The number of pulses per revolution is selected using position 8 of the switch described
in Section 4.5. The following chart shows the correct switch setting for each available
step resolution.

Switch

Position 8

Step

Resolution

Pulses Per

Revolution

0 (off)

Full-Step

200

1 (on)

Half-Step

400

J1

J2

MOTOR CURRENT &

STEP RESOLUTION
SWITCHES

Figure 4.1 Switches For Setting Current Level and Step Resolution