Tower installation

These installation instructions are intended to help you prepare before
your tower arrives. If discrepancies exist between these instructions
and those shipped with the tower, the instructions shipped with the
tower will govern.

1. Prior to placement of the tower, confirm that the supporting platform

is level, and that the anchor bolt holes are correctly located in accor-
dance with Marley drawings.

2. Place tower (or bottom module of AV6300 through AV6700) on your

prepared supports, aligning anchor bolt holes with those in your sup-
porting steel. Make sure that the orientation agrees with your intended
piping arrangement. Attach tower to supporting steel with four

1

2

" (13

mm) diameter bolts and flat washers (by others). Position flat washers
between the bolt head and the tower basin flange.

Remove the sheet metal fill protector shields from the bottom of the
top module before setting in place.

3.

aV6300 through aV6700 models only. Remove shipping guards from
bottom of top module (AV6500 thru AV6700). Clean any debris from
the underside of the top module fill, skid and beams and from the top
of the bottom module before hoisting into place.

Remove paper backing form sealer strips around top perimeter of
bottom module.

Place top module on the top peripheral bearing surface (factory-

installed gasket) of bottom module, aligning mating holes as it is set in
place. Attach top module to bottom module with fasteners provided—
according to Field Installation Manual instructions.

If tower purchased is one cell only, ignore steps 4 through 8.

4. If collection basins are to be equalized by the use of Marley standard

flumes, unbolt the temporary coverplate from the basin of the cell just
installed. The coverplate is located on the basin side.

5. Unbolt temporary coverplate from the basin of the 2nd cell and set

2nd cell (or bottom module of 2nd cell) in place. Align anchor bolt
holes and flume openings in basin sides.

6. Install flume according to

Field Installation Manual instructions.