Electrical Requirements

M414905

46

© Copyright, Alliance Laundry Systems LLC – DO NOT COPY or TRANSMIT

50 and 75 Pound Electric Models

Refer to Table 10.

NOTE: Wire size and breaker ratings were
obtained from the Canadian Electrical Code for
75 C. wire and are intended for use as a guideline
only. Electrical connections should be made by a
qualified electrical contractor in accordance with
all applicable local and national requirements.

NOTE: Electrical specifications below are subject
to change without notice. Always refer to product
serial plate for most current specifications of
product being installed.

NOTE: Use copper conductors only.

NOTE: Connect to individual branch circuit.

NOTE: 3 Phase Only – Each tumbler must be
connected to its own individual branch circuit
breaker, not fuses, to avoid the possibility of “single
phasing” and causing premature failure of the
motor(s).

Serial Plate Rating

Terminal Block

Connections

Required

Serial Plate Amps

Recommended Circuit

Nonreversing

Reversing

Breaker

Rating

Wire Size

AWG (mm

2

)

240V/50Hz/1ph
(50 Pound only)

L1, Neutral and Ground

93

95

125A – 1 pole

1 (42.4)

200-208V/60Hz/3ph

L1, L2, L3 and ground

89

88

125A – 3 pole

1 (42.4)

200V/50Hz/3ph

L1, L2, L3 and ground

84

85

125A – 3 pole

1 (42.4)

230V/50Hz/3ph

L1, L2, L3 and ground

73

75

100A – 3 pole

3 (26.7)

240V/50Hz/3ph

L1, L2, L3 and ground

79

78

100A – 3 pole

3 (26.7)

240V/60Hz/3ph

L1, L2, L3 and ground

79

78

100A – 3 pole

3 (26.7)

380V/50 or 60Hz/3ph L1, L2, L3 and ground

47

48

60A – 3 pole

6 (13.3)

400-415V/50Hz/3ph

L1, L2, L3 and ground

43

44

60A – 3 pole

6 (13.3)

440V/60Hz/3ph

L1, L2, L3 and ground

41

41

51A – 3 pole

6 (13.3)

480V/60Hz/3ph

L1, L2, L3 and ground

38

38

50A – 3 pole

6 (13.3)

Table 10