Installation Instructions

Piping Joints Thermal Insulation:
Wrap the piping joints with thermal
insulation materials and then wrap
with a vinyl tape.

Piping Thermal Insulation:

a. Place the drain hose under the piping.
b. Insulation material uses polythene foam over

in thickness.

Note: Drain hose is prepared by user.

3/8"

Drain pipe should point downward for easy drain flow.
Do not arrange the drain pipe twisted, sticking out or wave
around, do not immerse the end of it in water.

If an extension drain hose is connected to the drain pipe, make
sure to thermal insulated when passing along the indoor unit.

When the piping is directed to the right, piping, power
Cord and drain pipe should be thermal insulated and
fixed onto the back of the unit with a piping

.

connector

Thermal insulation

wrapped with vinyl type

Small
pipe

Large pipe

Thermal insulation
tube

Power cord 1
(for heat-pump)

Power cord

Defrost cable(for heat-pump)

Drain hose
(prepared by user)

A. Insert the pipe

to the slot.

connector

B. Press to hook the pipe

onto the base.

connector

Base

Base

Base

Piping

connector

Piping fixer

Hook here

Insert here

drain
hose

drain
hose

large
pipe

large
pipe

small
pipe

small
pipe

1

1

NOTE

NOTE

The temperature of refrigerant circuit
will be high, please keep the
interconnection able away from the copper tube.

c

Refrigerant Line Connection Torque Table

Flare Nut

Tightening Torque

1/4-3/8

"

1/4-1/2

"

1/2-3/4

"

7/8-1 1/8

"

25 Ft.LBs(350 Kg.Cm)

40 Ft.LBs(560 Kg.Cm)

60 Ft.LBs(840 Kg.Cm)

110 Ft.LBs(1540 Kg.Cm)

Tighten flares to below torques:

Connecting the refrigerant lines between the indoor& outdoor units

Note that since the refrigerant metering device is located in the outdoor unit,both refrigerant
lines must be insulated with a minimum of 3/8

foam along the entire length.

Gently bend the line set stubs from the indoor unit to the desired location and the using 2 box
end or adjustable wrenches,remove the flare nuts from the indoor unit line stubs.The indoor
unit is charged with a dry gas.If you do not hear the release of pressure when removing the
flare nuts,it is possible that the evaporator section(indoor unit)has developed a leak and you
should contact your dealer for a replacement indoor unit.Note:Using a small amount of
vacuum pump oil on the male flare threads will ease installation.Snug the line set to the stubs
using the 2 wrenches-one wrench on the male fitting and one wrench on the female fitting.

"