SPX Cooling Technologies CS4000 User Manual

Page 67

Advertising
background image

CS4000 Mini Controller with Ethernet

Page

5-8

T-38324-A

39-30-38324

There are three possible reasons that a flash fails:

The null modem cable has been inserted into the 9-pin connector (J7) on the
Ethernet interface card incorrectly.

The jumper (J1) labeled ‘Prog’ on the Ethernet interface card has been installed
incorrectly.

An incorrect cable has been used to connect the laptop to the Ethernet interface
card. You must use the GSE tech-motive tool null modem cable (part number
41-41-0109FN).

After checking the above points, repeat Steps 9, 10 and 11 until the error messages
fail to appear and the TINI Ethernet Flash Utility begins flashing the application file to
the Ethernet interface card.

NOTE: If you cannot successfully flash the Ethernet interface card from

your laptop computer, consult a GSE tech-motive tool engineer.

12. Confirm or change the IP address, subnet mask and default gateway.

When the application file is flashed to the Ethernet interface card, the Application
Settings window is displayed. This window allows you to confirm or change the IP
address, subnet mask and default gateway being used. See Figure 5-11.

Figure 5-11.

Confirming the IP Address, Subnet Mask and Default
Gateway

To confirm the current settings for the IP address, subnet mask and the default gateway,
click OK.

OR

Advertising