SS-460-001 2 I56-3850-005

figUre 3. TYpiCaL nOTifiCaTiOn appLianCe CirCUiT COnfigUraTiOn, nfpa STYLe Y:

(+)

(+)

(+)

(+)

(+)

(+)

47K EOL

RESISTOR

ELR-47K

UL LISTED EOL RELAY

SHOWN ENERGIZED

24 VDC COIL EOLR-1

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

TO NEXT CONTROL MODULE OR END-OF-LINE

RELAY. ONE RELAY REQUIRED FOR EACH

CIRCUIT. SOME CONTROL PANELS HAVE RELAY

BUILT IN AND DO NOT REQUIRE EXTERNAL

WIRING. REFER TO PANEL MANUAL.

24 VDC POWER SUPPLY

ISOLATED, REGULATED,

POWER LIMITED PER NFPA 70.

LISTED FOR FIRE PROTECTION

WITH BATTERY BACKUP.

MODULE POLARITIES ARE

SHOWN IN ALARM

CONNECT MODULES TO

LISTED COMPATIBLE

CONTROL PANELS ONLY

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED

AND POWER LIMITED

CONTROL

MODULE

FROM

PANEL OR

PREVIOUS

DEVICE

TO NEXT

DEVICE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS

LIMITED TO THAT ZONE AND DOES NOT

RESULT IN A FAULT IN A SEPARATE ZONE.

(−)

(−)

(−)

(−)

(−)

(−)

C0913-05

figUre 4. TYpiCaL faULT TOLeranT nOTifiCaTiOn appLianCe CirCUiT COnfigUraTiOn, nfpa STYLe Z:

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

(+)

(–)

ALL WIRING SHOWN IS SUPERVISED

AND POWER LIMITED

MODULE POLARITIES ARE

SHOWN IN ALARM

EOL RESISTOR

IS INTERNAL AT

TERMINALS

8 & 9

UL LISTED EOL

RELAY SHOWN

ENERGIZED

24 VDC COIL

EOLR-1

TO NEXT CONTROL MODULE OR

END-OF-LINE RELAY. ONE RELAY

REQUIRED FOR EACH CIRCUIT.

SOME CONTROL PANELS HAVE

RELAY BUILT IN AND DO NOT

REQUIRE EXTERNAL WIRING.

REFER TO PANEL MANUAL.

CONTROL

MODULE

TO

NEXT

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX. TWISTED PAIR

IS RECOMMENDED

CONNECT MODULES TO LISTED

COMPATIBLE CONTROL PANELS ONLY

FROM

PANEL OR

PREVIOUS

DEVICE

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11.

BREAK WIRE RUN TO PROVIDE SUPERVISION

OF CONNECTIONS.

24 VDC POWER SUPPLY

ISOLATED, REGULATED, POWER

LIMITED PER NFPA 70. LISTED

FOR FIRE PROTECTION WITH

BATTERY BACKUP.

*NOTE: ANY FAULT IN THE POWER SUPPLY

IS LIMITED TO THAT ZONE AND DOES NOT

RESULT IN A FAULT IN A SEPARATE ZONE.

C0914-05