System Sensor Supervised Control Module M500S User Manual

Page 3

Advertising
background image

SS-460-001 3 I56-3850-005

figUre 5. TYpiCaL Wiring fOr Speaker SUperviSiOn and SWiTChing, nfpa STYLe Y:

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

(+)

(–)

AUDIO CIRCUIT

DO NOT LOOP WIRE AROUND TERMINALS

10 & 11. BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

WIRES MUST BE

SUPERVISED PER NFPA

CONNECT MODULES TO LISTED COMPATIBLE

CONTROL PANELS ONLY

FROM PANEL OR

PREVIOUS DEVICE

CONTROL

MODULE

47K EOL

RESISTOR

ELR-47K

SPEAKERS MUST BE LISTED FOR FIRE PROTECTION.

TO NEXT

DEVICE

MODULE POLARITIES ARE

SHOWN IN ALARM

TO NEXT CONTROL MODULE

LAST MODULE MUST RETURN

WIRES FOR SUPERVISION

SUPERVISION

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.

AUDIO AMPLIFIER, 70.7 Vrms MAX.

AMPLIFIER MUST PROVIDE WIRING

SUPERVISION PER NFPA.

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C0915-05

figUre 6. TYpiCaL faULT TOLeranT Wiring fOr Speaker SUperviSiOn and SWiTChing, nfpa STYLe Z:

(+)

(–)

(+)

(–)

(+)

(–)

(+)

(–)

(–)

(+)

(–)

(+)

ALL WIRING SHOWN IS SUPERVISED

AND POWER LIMITED

TO NEXT

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

WIRES MUST BE

SUPERVISED PER NFPA

CONNECT MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY

FROM

PANEL OR

PREVIOUS

DEVICE

CONTROL

MODULE

SPEAKERS MUST BE LISTED FOR

FIRE PROTECTION.

47K EOL RESISTOR

IS INTERNAL AT

TERMINALS 8 & 9

MODULE POLARITIES ARE

SHOWN IN ALARM

TO NEXT CONTROL MODULE

LAST MODULE MUST RETURN

WIRES FOR SUPERVISION

SUPERVISION

AUDIO CIRCUIT WIRING MUST BE TWISTED PAIR AS A MINIMUM. SEE PANEL INSTALLATION MANUAL FOR DETAILED INFORMATION.

AUDIO AMPLIFIER, 70.7 Vrms MAX.

AMPLIFIER MUST PROVIDE WIRING

SUPERVISION PER NFPA.

AUDIO CIRCUIT

DO NOT LOOP WIRE AROUND TERMINALS

10 & 11. BREAK WIRE TO ENSURE

SUPERVISION OF CONNECTIONS.

BYPASS CAPACITORS: 100µ

A2143-20 NONPOLARIZED

<10µA LEAKAGE

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C0916-05

Advertising