5 auto-tuning smc series chillers – Sterling Power Products SMC 1/2 - 1 1/2 Portable Chiller User Manual

Page 29

Advertising
background image

SMC Series Chillers

Page 29

Important!

Do not change any of the control settings without consulting

the Sterling Service Department.

The AEC, Inc. warranty does not cover chiller failures

from tampering with controller settings!

Down Key

Each press of the

Down Arrow

key decrements or reduces

the values or settings on the

SV

display.

Up Key

Each press of the

Up Arrow

key increments or advances

the values or settings on the

SV

display.


5-5 Auto-Tuning SMC Series Chillers

The Auto-Tune function lets you fine-tune the control PID to
process requirements. Activate the Auto-Tune function whenever
the process under control changes. Don't be alarmed by control
response. It may take the process temperature above and below the
set points as many as three (3) times. It will then level off and
control to the process set point. Auto tuning can take up to 45
minutes
, and is best done before any product is being run.

Important!

Factory default settings are: P = .3, I = 7, and D = 1

To auto-tune the controller:

„ Press and hold down the

AT

AT

key for several seconds until

the

AT

indicator flashes.

„ The

AT

LED flashes to indicate that the control is tuning

itself.When the

AT

LED light stops flashing, the controller is

tuned and ready for operation.