8 troubleshooting guide – Sterling Power Products SMC 1/2 - 1 1/2 Portable Chiller User Manual

Page 37

Advertising
background image

SMC Series Chillers

Page 37

8 Troubleshooting

Guide

Problem

Cause

Solution

Chiller will not run.


No power.

Check main disconnect
fuses, wiring, and power
lead to the unit.

Wrong voltage supplied to
the chiller.

Voltage must be within plus
or minus 10% of the
nameplate rating.

Defective on/off switch.

Replace.

Control circuit fuse blown.

Replace, check the
transformer.

Defective

control

transformer.

Replace.

Pump runs, compressor
cycles at short intervals.

No process load on the
chiller.

Increase the process load.

Refrigerant is low.

Check the refrigerant
charge.

The leaving water
temperature is too high.

Refrigerant is low.

Check the refrigerant
charge.



Improper water/glycol
solution.

Make sure that the coolant
solution is right for the
process — must be 75%
water and 25% glycol.
See

Figure 6

on page 16

for more information.

Pump pressure is low (see
pump curves).

Check for foreign matter.

Clean the system.

Pump pressure is too high.


Restricted water flow.

Check for partially closed
valves, etc. Be sure all
lines are properly sized.

Advertising