INSTALLATION AND EXTERNAL CONNECTION

Output Connection

- If the door lock is in POWER FAIL SAFE mode: (Door 1: Relay #1, Door 2: Relay #3)

Connect the COM line of the Door Lock relay to DC +12V.

Connect the plus (+) line of the Door Lock to the Normal Close (NC) line of the Door Lock relay.

Connect the minus (-) line of the Door Lock to GND (-).

- If the Door Lock is in POWER FAIL SECURE mode: (Door 1: Relay #1, Door 2: Relay #3)

Connect the COM line of the relay to DC +12V.

Connect the plus (+) line of the Door Lock to the Normal Open (NO) line of the Door Lock relay.

Connect the minus (-) line of the Door Lock to GND (-).

Alarm Device Connection (Door 1 Alarm: Relay #2, Door 2 Alarm: Relay #4)

Connect the COM line of the alarm device relay to DC +12V.

Connect the plus (+) line of the alarm device to the NO line of the alarm device relay.

Connect the minus (-) line of the alarm device to GND (-).

Door Number

Door Lock

Alarm Device

Note

Two Door Control

1

Relay Output #1

Relay Output #2

2

Relay Output #3

Relay Output #4

Three Door Control

1

Relay Output #1

Relay Output #2

2

Relay Output #8

Relay Output #9

I/O Board

3

Relay Output #10

Relay Output #11

I/O Board

Four Door Control

1

Relay Output #1

Relay Output #2

2

Relay Output #3

Relay Output #4

3

Relay Output #8

Relay Output #9

I/O Board

4

Relay Output #10

Relay Output #11

I/O Board

1.

2.

3.

1.

2.

3.

1.

2.

3.

Door Lock

POWER FAIL SAFE

POWER FAIL SECURE

GND

Alarm Device

DC +12V

GND

NC

COM

COM

NO