2.3 Linking the PIM-485-16-TD-NXT to WAPMs

2.3.1 How to Set an RF Channel

One of fifteen RF channels can be set using DIP switch SW7 on the PIM. Table 2-5 shows how to set
SW7 to select the desired RF channel:

Channel

Switch 1

Switch 2

Switch 3

Switch 4

1

up up up Up

1

up up up

down

2

up up

down

Up

3

up up

down

down

4

up down up Up

5

up down up down

6

up down

down Up

7

up down down down

8

down up up Up

9

down up up down

10

down up down Up

11

down up down

down

12

down down up

Up

13

down down up down

14

down down down Up

15

down down down down

Table 2-5 – DIP Switch Setting to Select the RF Channel

NOTE: The first two switch settings select Channel 1.

2.3.2 Linking WAPM’s using the Configuration & Demonstration Tool (CDT)

The Schlage CDT can be used to link WAPM’s to a PIM-485-16-TD-NXT. Refer to the CDT

The PIM-485-16-TD-NXT must be connected to the PC running the CDT using a serial connection
(either RS485 or RS232).

Once the PIM-485-16-TD-NXT is connected to the PC and the CDT is running the Link tab on the
CDT’s PIM panel is used to control the PIM-485-16-TD-NXT’s Link Mode. The Panel field needs to
be set to indicate which WAPM is to be linked. Table 2-6 shows the allowable range of values for the
Panel field on the CDT Link tab.

PIM Model

Panel Field

PIMx-485-16-NEX 0-15

Table 2-6 – CDT Panel Field Range of Values