Siemens Electric Actuators For Butterfly Valves SQU83 User Manual

Page 5

Advertising
background image

5/8

Siemens Building Technologies

Electric actuators for butterfly valves

CM1N4506en

HVAC Products

07.06.2004

Mounting

Mounting instructions are enclosed with the mounting kit.
The valve, actuator and mounting kit are packed separately. The valve and actuator
can be assembled easily on site. There is no need for special tools or calibration.
Take care to install the valve the right way up. Refer to the mounting instructions for the
valve concerned (butterfly or slipper valves).

90°

43

62

Z

0

1

90°

Commissioning

When commissioning the complete motorised valve, consisting of actuator, mounting kit
and (butterfly or slipper) valve, check the wiring and test the functions. This also
applies to any additional components fitted (e.g. auxiliary switch or potentiometer).

Siemens slipper valves up to DN50 can be commissioned without an actuator being
fitted. In this case, the flow rate must be adjusted manually with the standard manual
adjuster fitted to the valve.

For automatic operation, the rotary switch must be set to "AUTO".

"AUTO" = Automatic operation

"MAN" = Manual operation


The actuators are factory-set to rotate in a clockwise direction (as seen from the front).
The direction of rotation can be reversed by repositioning a connector located under the
cover (see "Mechanical design").
The wiring for the OPEN and CLOSE control signal is not affected.

As supplied

Direction of rotation reversed




.
.
.
.
.
.
.
.
.
.
.

Orientation

Note

Mode of operation

Rotary switch for
mode selection

Reversing the
direction of rotation

Advertising