Siemens Electric Actuators For Butterfly Valves SQU83 User Manual

Page 6

Advertising
background image

6/8

Siemens Building Technologies

Electric actuators for butterfly valves

CM1N4506en

HVAC Products

07.06.2004

The angle of rotation is factory-set to 90°. However, the angle can be changed to
between 70° and 180°. This may be necessary when using non-Siemens valves.
Special notes on this subject will be found in the mounting instructions for the ASK40
and ASK41 (mounting kits for non-Siemens valves).

Maintenance

The actuators require no maintenance.
When servicing the valve and/or actuator: switch OFF the pump and power
supply, close the main shut-off valve in the pipework, release pressure in the
pipes and allow them to cool down completely.
If necessary, disconnect electrical connections from terminals.

Disposal

The device may not be disposed of together with domestic waste.

This applies in

particular to the PCB.
Legislation may demand special handling of certain components, or it may be sensible
from an ecological point of view.

Current local legislation must be observed.

Warranty

The technical data given for these applications is valid only in conjunction with the
Siemens valves (butterfly and slipper valves) and third-party valves for use with the
ASK40 / ASK41, as described under "Compatibility". The use of third-party valves
other than those recommended by Siemens invalidates the warranty.

Technical data

Power supply

Rated voltage
SQK33.00, SQL33.00, SQL33.03
SQL83.00


AC 230 V ± 15 %
AC 24 V ± 20 %

Rated frequency

50 / 60 Hz

Control

signal

3-position

Power

consumption

*)

SQK33.00
SQL33.00, SQL83.00
SQL33.0...


3 VA
4 VA
6.5 VA

Operating data

Run-time for rotation through 90°

at 50 Hz

at 60 Hz

SQK33.00, SQL33.00
SQL83.00
SQL33.03

125 s
125 s

30 s

105 s
105 s

25 s

Angle

of

rotation

Factory setting
Adjustment range


90° ± 2°
70° ...180°



Setting the angle of
rotation

.

Warning !

.
.
.
.
.
.
.
.
.
.

Advertising