Venting, Vent terminals, Pressure switches – State Industries ROOFTOP SRT80 120NE User Manual

Page 15: Gas piping

Advertising
background image

15

VENTING

WARNING

THE INSTRUCTIONS IN THIS SECTION ON VENTING MUST
BE FOLLOWED TO AVOID CHOKED COMBUSTION OR
RECIRCULATION OF FLUE GASES. SUCH CONDITIONS CAUSE
SOOTING OR RISKS OF FIRE AND ASPHYXIATION.

WARNING

NEVER OPERATE THE HEATER UNLESS IT IS VENTED TO
THE OUTDOORS AND HAS ADEQUATE AIR SUPPLY TO AVOID
RISKS OF IMPROPER OPERATION, FIRE, EXPLOSION OR
ASPHYXIATION.

CAUTION

DO NOT TERMINATE THE VENTING WHERE NOISE FROM THE
EXHAUST OR INTAKE WILL BE OBJECTIONABLE. THIS
INCLUDES LOCATIONS CLOSE TO OR ACROSS FROM WINDOWS
AND DOORS.

FIGURE 33

VENT TERMINALS

The vent system must terminate so that proper clearances are
maintained as cited in local codes or the current edition of the
National Fuel Gas Code, ANSI Z223.1/NFPA 54.

The SRT80-120NE series is designed with an internal vent
construction. The exhaust vent terminal and the inlet air terminal
are located on the sides of the appliance. Do not add vent pipe to
the appliance, see Figure 33.

Assure the exhaust vent terminal is not in a public area where the
hoods are exposed. The exhaust vent terminal gets very HOT
during operation and can cause burns. Please use caution when
working around the exhaust vent terminal.

It is imperative that the area around the vent terminal hoods are
kept clear from obstructions so plenty of fresh air is available for
combustion.

The vent shall terminate a minimum of 12" (30.5 cm) above expected
snowfall level to prevent blockage of vent termination.

WARNING

USE ONLY THE VENT TERMINALS SUPPLIED WITH THIS UNIT.
TERMINATION OF A VENT SYSTEM WITH A DEVICE OTHER
THAN THE SUPPLIED VENT TERMINATIONS WILL AFFECT
SYSTEM PERFORMANCE AND RESULT IN A SAFETY HAZARD.

PRESSURE SWITCHES

The SRT80-120NE is provided with three pressure switches.
These switches are essential to the safe and proper operation of
the unit. All switches are wired in series. The controller is set up to
shut the unit down whenever there is a failure of any of the switches.

CAUTION

THE WATER HEATER IS POLARITY SENSITIVE. BEFORE
APPLYING ELECTRICITY TO THIS HEATER BE CERTAIN THAT
SUPPLY NEUTRAL WIRE TO GROUND CHECK INDICATES ZERO
VOLTAGE.

GAS PIPING

Contact your local gas service company to ensure that adequate
gas service is available and to review applicable installation codes
for your area.

TABLE 3

MAXIMUM CAPACITY OF PIPE IN CUBIC FEET OF GAS PER HOUR

(Based upon a Pressure Drop of 0.5 inch Water Column

and 0.6 Specific Gravity Gas

Size the main gas line in accordance with Table 3. The figures
shown are for straight lengths of pipe at 0.5 in. (125 kPa) W.C.
pressure drop, which is considered normal for low pressure
systems. Note that fittings such as elbows and tees will add to the
pipe pressure drop.

CAUTION

DO NOT USE FLEXIBLE GAS PIPING.

LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

INPUT IN THOUSANDS BTU/HR

FEET

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

10

175

360

680

1400

2100

3960

6300

11000 23000

20

120

250

485

950

1460

2750

4360

7700

15800

30

200

375

770

1180

2200

3520

6250

12800

40

170

320

660

990

1900

3000

5300

10900

50

151

285

580

900

1680

2650

4750

9700

60

138

260

530

810

1520

2400

4300

8800

70

125

240

490

750

1400

2250

3900

8100

80

220

460

690

1300

2050

3700

7500

90

205

430

650

1220

1950

3450

7200

100

195

400

620

1150

1850

3250

6700

125

175

360

550

1020

1650

2950

6000

150

160

325

500

950

1500

2650

5500

175

145

300

460

850

1370

2450

5000

200

135

280

430

800

1280

2280

4600

LENGTH

NORMAL IRON PIPE SIZES (INCHES)

IN

INPUT IN KW

METERS

1/2"

3/4"

1"

1 1/4" 1 1/2"

2"

2 1/2"

3"

4"

3.0

51

105

199

410

615

1160

1845

3221

6735

6.1

35

73

142

278

428

805

1277

2255

4626

9.1

59

110

225

346

644

1031

1830

3748

12.2

50

94

193

290

556

878

1552

3192

15.2

44

83

170

264

492

776

1391

2840

18.3

40

76

155

237

445

703

1259

2577

21.3

37

70

143

220

410

659

1142

2372

24.4

64

135

202

381

600

1083

2196

27.4

60

126

190

357

571

1010

2108

30.5

57

117

182

337

542

952

1962

38.1

51

105

161

299

483

864

1757

45.7

47

95

146

278

439

776

1610

53.3

42

88

135

249

401

717

1464

61.0

40

82

126

234

375

688

1347