Summary of arming sequences, Battery maintenance – Skylink SC-100 User Manual

Page 14

Advertising
background image

23

Below is a table summarizing all the preprogrammed sequences.

Sequence Zone 1 Zone 2 Zones 3 & 4 When sequence should be used

FOR TESTING

MPIN A #

chime

chime

chime

use for testing after installation
and to test batteries, also use as
a subtle chime when a remote
sensor has been activated

BASIC PROGRAMMING

MPIN B C

exit delay

off

instant

use when leaving the premises

(after 45 sec.)entry delay

entry delay instant

and no one is inside

MPIN C

exit delay

off

instant

use when leaving the premises

(after 45 sec.)

and someone is inside the
premises

MPIN A B

instant

off

instant

use when people are in the
premises and no one is expected
to enter/exit

MPIN #

off

off

off

turns off the system

Note: when MPIN # is enter and the system is already off, the system will default
back to the last sequence before the unit was shut off

ADVANCED PROGRAMMING

MPIN A A

entry delay off

instant

someone is in the building and
someone is expected to enter/
no exit delay

MPIN A C

entry delay entry delay instant

person staying in the premises
is setting the alarm and will not
walk in the area monitored by the
motion detector

Panic button - The SC-100 has 2 panic buttons, (the red buttons on the keychain
transmitter and on the Control Panel). The alarm will sound instantly when either
of these buttons are pressed whatever mode you are in.

Emergency Silent Alarm (works in conjunction with the Emergency Dialer option) -
When disarming the system under duress, enter your MPIN, then press [ B ], [ B ].
This will terminate the delay mode and return to the previous arm mode, as well
as send a signal to the Emergency Dialer, which will then send pre-recorded
messages for help. Do not activate this sequence if your Skylink security system
contains the Audio Alarm AA-433. Since it will sound the siren of the AA-433
instantly.

When both power sources are removed from the Control Panel, (the AC adapter
is unplugged and the battery is removed), all sequences will return to the above
factory default.

SUMMARY OF ARMING SEQUENCES

The SC-100 Security System comes with 5 batteries that at some point you may
have to replace:

1

9 volt alkaline battery for the Control Panel

1

9 volt alkaline battery for the Motion Sensor

2

12 volt alkaline batteries for the 2 Door/Window Sensors

1

12 volt alkaline battery for the Keychain Transmitter

Recommendation: Test you system periodically to ensure that all batteries are
working.

CONTROL PANEL BATTERY

The Control Panel comes equipped with a backup battery in case the electrical
power is interrupted for any reason.

When the Control Panel battery is low, the LOBATT. light goes on. Also, when the
LOBATT. light is on and if you press any key on the keypad, 10 beeps warn you
that the battery needs to be changed.

To replace the Control Panel backup battery:

1. Disarm the unit.

2. Open the Control Panel case by pressing
down on the two tabs on the top edge and
pull the front forward.

3. Disconnect the old battery.

4. Connect the new battery.

5. Close the Control Panel.

Note: To guard against sabotage, the Control Panel is equipped with an emer-
gency switch that activates the alarm instantly when the case is opened. Make
sure that the unit is disarmed when you open the case or you will activate the
alarm.

The battery life, (9 volt alkaline battery), is approximately two years if used only
for backup.

Note: If the AC adapter is disconnected while the battery is replaced, the security
system will erase all the modifications that have been made and return to the
factory default. Also, your MPIN will return to 000.

24

BATTERY MAINTENANCE

Advertising