System Sensor DH400ACDCP User Manual

Page 10

Advertising
background image

[7.2] Photo Heads
1. Remove the detector cover by inserting a small bladed

screwdriver into the slot located 90 degrees from the
field test port. Rotate the cover counterclockwise to re-
move (see Figure 13).

2. Lift the screen from the photo chamber. Vacuum the

screen and cover before using clean, compressed air to
loosen and blow out any remaining debris. Replacement
screens (RS24) are available.

3. Vacuum the photo chamber. Use clean compressed air

to blow it clean.

4. Replace the screen by aligning the arrow on top with

the field test port on the detector. Press the screen into
place. It should fit tightly on the chamber.

5. Replace the detector cover and rotate it clockwise to

lock it in place.

[7.4] Reinstallation
1. Reinstall the detector in its housing.
2. Restore system power.
3. Perform Detector Check, Section [5.7].
4. Notify the proper authorities testing has been completed

and the smoke detector system is back in operation.

DETECTOR

HEAD

TEST COIL

Figure 12. RTS451/RTS451KEY test coil installation:

H0245-00

D400-13-00

10

I56-0555-010R

Sensor

Cover

Sensing

Chamber

Cover and

Screen

Cover

Removal

Tabs

Sensing

Chamber

Optional

Thermistors

(2151T only)

Figure 13. Photo head exploded view:

C0892-00

Advertising