System Sensor DH400ACDCP User Manual

Page 6

Advertising
background image

24V

120 VAC

220/240

VAC

1

2

12

13

14

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC.

15

16

17

18

19

20

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.

TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS

REMOVED, AND DURING RESET. OPEN CONTACTS

SIGNAL TROUBLE CONDITION TO PANEL

.

24V

120 VAC

220/240

VAC

1

2

12

13

14

AVAILABLE POWER INPUTS

ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN, ETC.

15

16

17

18

19

20

N.C.

C.

N.O.

N.O.

C.

N.C.

ALARM AUXILIARY CONTACTS SHOWN IN STANDBY. CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS.

TROUBLE CONTACTS

TROUBLE CONTACTS CLOSED IN ALARM AND STANDBY. CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS

REMOVED, AND DURING RESET. OPEN CONTACTS

SIGNAL TROUBLE CONDITION TO PANEL.

11

10

11

10

8

9

ALARM INITIATION CONTACTS

CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM.

8

9

ALARM INITIATION CONTACTS

CONTACTS SHOWN OPEN IN STANDBY. CONTACTS CLOSE IN ALARM.

ALARM INITIATION LOOP

UL LISTED CONTROL PANEL

FIRST DETECTOR IN THE LOOP DH400ACDC

P

LAST DETECTOR IN THE LOOP DH400ACDC

P

EOL RESISTOR SPECIFIED BY PANEL MANUFACTURER

CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR. SEE SPECIFICATIONS FOR ADDITIONAL POWER SUPPLY INFORMATION.

FOR WIRING OF AUXILIARY DEVICES, REFER TO MANUFACTURER'S INSTALLATION INSTRUCTIONS OR CONTACT MANUFACTURER.

POWER INPUTS ACCEPT 24 VDC, 24 VAC 50-60 HZ, 120 VAC 50-60 HZ, OR 220/240 VAC 50-60 HZ. CONNECT POWER SOURCE TO APPROPRIATE TERMINALS OF EACH DETECTOR.

AUX. CONTACT RATINGS 10A @ 30 VDC 10A @ 250 VAC 500mA MINIMUM @ 24 VDC NOT INTENDED FOR CONNECTION TO CONTROL PANELS.

TROUBLE CONTACT RATING 0.3 A @ 32 VAC/DC

CAUTION

Do not loop wire under terminals when wiring detectors. Break wire runs to provide system supervision of connections.

Figure 7. System wiring diagram for duct detectors using a UL listed control panel (see Figure 9 for wiring of
optional accessories):

H0252-00

D400-13-00

6

I56-0555-010R

Advertising