Recold, Jw series, Construction – SPX Cooling Technologies Recold JW Series User Manual

Page 3

Advertising
background image

Recold

/

JW Series

Fluid Cooler

/

Construction

3

The JW Evaporative Fluid Cooler is a ruggedly built unit constructed to provide many years of durable,

dependable service with minimal maintenance requirements. Quality materials and workmanship are a key

factor in meeting this objective.

FAN MOTORS

Fan motors furnished as standard equipment are open

drip-proof type suitable for outdoor service. Motors

have a 1.15 service factor and are mounted on a

heavy duty adjustable base located for easy access.

FAN GUARD SCREENS

All moving parts are protected with OSHA approved

galvanized steel screens. Each guard is easily

removed for access to the fan.

FAN SECTION

The centrifugal fan is

forward curved, statically

and dynamically balanced

and constructed of

galvanized steel. The fan

housing has curved inlet

rings for efficient air entry

and discharge into the

pan. Fans are mounted

on a solid steel shaft

coated to resist corrosion.

Heavy duty, pillow block

type, self-aligning ball

bearings are located at

each end of the fan shaft.
No intermediate bearings are

required
Extended lube lines are supplied as standard

equipment to allow servicing bearings without

removal of fan guard screens.

WATER CIRCULATION PUMP

The water circulation pump is a close coupled, bronze

fitted centrifugal type with mechanical seal. Each

pump is factory mounted and piped. Standard motor

is open drip-proof suitable for outdoor service.

DRIFT ELIMINATORS

Eliminators are constructed of PVC assemblies in

removable, easy to handle sections. Each section has

a three break design allowing three changes in air

flow and measure approximately 5 inches in depth.

The use of durable PVC eliminates the corrosion

problems associated with galvanized eliminators.

HEAT EXCHANGE COIL

Coil tube bundle is constructed of

5

8

" copper

tubing with stainless steel tube sheets

and copper headers. The copper

construction offers a

noncorrosive coil for extended

service life.

ACCESS DOORS

Large rectangular access

doors are strategically

located to provide access

to both upper water

distribution system and

lower pan basin. The

patented doors provide a

complete air and water tight

seal without the use of

gaskets or fasteners

WATER MAKE-UP

Water make-up is provided

by a solid brass float valve with arm

and float ball installed in an external float

b o x . This allows easy observation of the water

operating level and maintenance of the valve with unit

in operation.

Construction:

The Evaporative Fluid Cooler sump pan is constructed of 300 stainless steel and casing panels

are constructed of heavy gauge, G-235 galvanized steel. The sump pan and casing panels are flanged outward

so that all the connecting fasteners are located outside the flooded section of the unit to help prevent leaks

in the unit and provides a more permanent watertight joint. To provide further protection from corrosion, no

welded joints are located below the water line. The unit is designed for a 30 psf on any projected area and ships

in one piece on a minimum 6" high stainless steel channel base to help in handling and installation of the unit.

Advertising