Recold, Jw series, Freeze protection – SPX Cooling Technologies Recold JW Series User Manual

Page 6: Fluid cooler

Advertising
background image

Recold

/

JW Series

Fluid Cooler

/

Freeze Protection

6

For the most part, evaporative closed circuit coolers

will be installed for operation on a year-round basis.

Units installed in a cold climate must be provided with

adequate freeze protection for both the recirculating

water and the heat exchange coil for proper

equipment operation and maintenance.

RECIRCULATING WATER

The operation of evaporative cooled equipment under

approximately full load conditions will prevent freezing

of the recirculated water. However, during periods of

very little or no heat load when fans and pumps are

shut down, some form of freeze protection must be

used.
A simple form of freeze protection commonly used

is a remote sump tank inside a heated building

below the evaporative cooled equipment. The water

circulation pump is located at the remote tank

circulating water through the evaporative cooler

during load conditions. When the unit is shut down,

the water drains down into the remote sump tank

which is in a heated atmosphere.
The remote sump installation may be unacceptable in

some cases due to unit location or space limitations.

For these applications, pan water freeze protection

may be attained by means of an optional electric

heater located inside the unit pan. Electric pan

heaters are designed to prevent pan water freezing

during unit shut down with fans and pumps idle.
Water lines to and from the unit, pump, pump

discharge and drain lines must be wrapped with a

heat-tracing element and insulated to protect them

from freezing.

HEAT EXCHANGE COIL PROTECTION

The best means of heat exchanger coil freeze

protection is to circulate an ethylene glycol water

solution. The solution freeze points with respective

ethylene glycol by volume are given in Table 11

below. This method will allow freeze protection

irrespective of heat load or unit shut down.
Some applications will not permit the use of an

ethylene glycol solution. Under these circumstances,

other means of freeze protections must be used and

the following rules strictly adhered to.
1. Maintain full flow through the coil
2. Maintain heat load on the coil at all time so that the

leaving water temperature does not drop below

+50°F

Full flow alone will not protect the coil.

Temperature of +50°F must also be maintained.
Methods of maintaining the recommended fluid

temperature may vary with system design and

operation. A simple means of preventing heat loss

may be to locate the unit indoors allowing a heated

atmosphere. Adequate space and ductwork must be

provided for proper operation.
Units operating in low ambient conditions with a

heat load which becomes very low or drops off

completely may require the addition of an artificial

load to maintain safe fluid temperature. The amount

of artificial load required may be reduced by means

of discharge positive closure dampers. The addition

of the dampers will prevent induced air circulation or

the chimney effect which may occur during unit shut

down.
The above methods of coil freeze protection, when

properly applied and maintained will provide good

equipment protection. All methods, other than

those using an adequate antifreeze solution, should

provide a means of emergency coil draining. It is

recommended that automatic drain valves and air

vents with vacuum breakers be installed on each

coil circuit. Adequately size drains with heat-tracing

tape and insulation should be provided for free

drainage. Should the circulating pump fail or the water

temperature leaving the coil drop below 50°F for any

reason, the coil will automatically drain preventing

freeze damage.

Freeze

Point °F

Ethylene Glycol (by volume)

20%

30%

40%

50%

14

3

-14

-38

Unit Model

JW/JWL

Ethylene

Glycol

By Volume

Design Flow GPM

40

50

70

90

100

125

150

175 Above

10A thru 35C

20%

1.07 1.05 1.02 1.00 1.00 1.00 1.00 1.00

1.00

30%

1.10 1.07 1.02 1.01 1.00 1.00 1.00 1.00

1.00

40%

1.14 1.11 1.05 1.01 1.00 1.00 1.00 1.00

1.00

50%

1.16 1.13 1.06 1.01 1.00 1.00 1.00 1.00

1.00

50A thru 50C

20%

1.12 1.09 1.05 1.03 1.02 1.00 1.00 1.00

1.00

30%

1.16 1.12 1.07 1.04 1.02 1.00 1.00 1.00

1.00

40%

1.19 1.16 1.11 1.06 1.04 1.01 1.00 1.00

1.00

50%

1.23 1.21 1.14 1.08 1.05 1.01 1.00 1.00

1.00

70B thru 130C

20%

1.15 1.11 1.09 1.06 1.04 1.03 1.01 1.00

1.00

30%

1.18 1.11 1.07 1.05 1.03 1.01 1.00

1.00

40%

1.20 1.15 1.10 1.07 1.05 1.03 1.00

1.00

50%

1.23 1.20 1.11 1.11 1.07 1.04 1.00

1.00

Table 1 Glycol Flow Correction Factors

Advertising