Danger – Schneider Electric POWERLOGIC PWRSRV750 User Manual

Page 10

Advertising
background image

Chapter 3—Installation

63230-216-207/A3

Mounting

9/2002

© 2002 Schneider Electric All Rights Reserved

6

Mount the Power Server and Power Supply only in a horizontal position as
shown in Figure 3–3.

Figure 3–3: Proper orientation of Power Server and power supply

To mount the Power Server on a DIN rail, follow these steps:

1. Turn off power to the Power Server and any equipment into which it is to

be installed and verify that power is off.

2. Ensure that the DIN rail is attached horizontally to a surface with a

minimum thickness of 0.078 in (2 mm) for stability.

3. Place the Power Server on the DIN rail with the upper slot first. Then push

against the lower edge to snap it on the rail.

DANGER

HAZARD OF ELECTRIC SHOCK, BURN, OR EXPLOSION

• Turn off all power supplying this equipment and the equipment in which

it is installed before working on this equipment.

• Always use a properly rated voltage sensing device to confirm that

power is off.

Failure to follow these instructions will result in death or serious
injury.