TABLE 5

Feed water makeup requirements.

NOTE

These recommendations are considered normal for
compact buildings on the basis of 80% receiver use.
Where buildings are spread out, additional receiver
capacity may be necessary because of the extended
time required for condensation to return to the receiver.

9.

WATER PIPING

See FIGURE 5 for acceptable water piping diagram. TABLE
6 gives pumping rate and supply & return sizing for standard
installations.

TABLE 6

Based on 20

°

F system temperature drop.

NOTE

Boiler supplied with 4" water supply tapping and 3" return
tapping.

FIGURE 5

10. TANKLESS HEATERS
Heater openings are provided for below-the-water-line tankless
heater coils in all special intermediate sections when ordered.
See TABLE 2 for the conr•ct placement of these heater
sections. Install the low limit temperature control in the 3/4"
tap located in the center of the coil.

If the heater sections are installed in an order other than in
TABLE 2 the jacket panels will not match.

11. SMOKE HOOD
Install smoke hood with the correct size smoke pipe
connecting collar using the 5/16" x 1-1/2" studs and hex nuts
furnished in screw seats in the back section. Apply self-
adhesive insulating tape (Items 21 and 22 in Parts detail
drawing on Page 2) to smoke hood flange and damper angle
Item 23. Fasten the slide damper in the open position for
starting the burner adjustment process.

See FIGURE 6 for recommended “L” coil piping and FIGURE
7 for SM9-18 single and/or dual piping arrangements.

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

PAGE 6

3

4

5

6

7

8

9

10

11

12

.61

.85

1.19

1.52

1.86

2.19

2.53

2.86

3.20

3.53

1.4

1.9

2.4

2.9

3.3

3.8

4.3

4.8

5.2

5.7

1.22

1.70

2.37

3.04

3.71

4.38

5.05

5.72

6.39

7.06

12

16

22

29

35

41

47

54

60

66

NUMBER

OF

SECTIONS

EVAPOR.

RATE

GPM

WATER 1"

BELOW WATER

LEVEL GAL.

MIN. FEED

WATER PUMP

RATE-GPM

CONDENSATE

RECEIVER

CAP.-GAL.

BOILER SIZE

GPM

RETURN CONN.

SUPPLY CONN.

3

4

5

6

7

8

9

10

11

12

30

41

58

74

90

106

123

139

155

171

2"

2"

2-1/2"

3"

3"

3"

3"

3"

3"

3"

2"

2"

2-1/2"

3"

3"

3"

3"

3"

4"

4"

GATE VALVE

SUPPORT RELIEF VALVE

DISCHARGE PIPE

TERMINATE DISCHARGE

PIPE SO AS TO AVOID

DISCHARGE ON PERSONS

SYSTEM RETURN

CONNECTION

BLOWDOWN VALVE

TO DRAIN

GATE VALVE

TYPICAL WATER PIPING DIAGRAM

RELIEF VALVE

PRESSURE
REGULATING
VALVE

GATE

VALVE

CIRCULATOR

EXPANSION
TANK

AIR REMOVAL
PIPING

CHECK VALVE

C.W. MAKEUP
CONNECTION

SYSTEM SUPPLY

CONNECTIONS