19a series boiler installation instructions – Smith Cast Iron Boilers 19A SERIES User Manual

Page 7

Advertising
background image

FIGURE 6 — TANKLESS PIPING

FIGURE 7 — DUAL TANKLESS PIPING

12. BURNER MOUNTING PLATE & TARGET WALL
The new target wall used on 3-6 section boilers must be
positioned with the flat side tight against the rear casting
and with the bottom side resting on the floor of the combustion
chamber. No glues or fasteners are used to secure the target
wall.

Each boiler is provided with a cast iron burner mounting
plate with an appropriate burner opening and tapped holes
for studs to accommodate burner flange. The mounting plate
is furnished with 1/4" diameter sealing rope and an insulation
block which should be installed on the plate before placing
the plate on the boiler. (See exploded view on page 2, Items
11-13 & FIGURE 8.)

19A SERIES BOILER

INSTALLATION INSTRUCTIONS

PAGE 7

HOT
WATER
SUPPLY

OUT

IN

UNIONS

GATE VALVE

TEMPERING VALVE

FLOW LIMITING VALVE

TEMPERATURE GAUGE

OPERATING
CONTROL

TANKLESS

HEATER

TEMPERED
WATER
SUPPLY

COLD
WATER
INLET

OUT

IN

OUT

IN

GATE VALVE

HOT
WATER
SUPPLY

UNION

GATE VALVE

TEMPERING VALVE

FLOW LIMITING VALVE

TEMPERATURE GAUGE

OPERATING
CONTROL

TANKLESS

HEATER

TEMPERED
WATER
SUPPLY

COLD
WATER
INLET

The sealing rope should be placed in the groove on the
boiler side of the plate using adhesive to hold it in place. The
insulation block has a burner opening and a cutout for the
observation opening. Locate the block with the high
temperature facing on the fire side in the opening in the front
section. The burner mounting plate insulating block for
Beckett burners is installed with the dished side facing
towards the combustion chamber.

Attach the block to the plate with the four 1/4" x 5" machine
screws and 1-1/2" O.D. washers, the washers on the insulation
block side. At the time of burner installation, the hole in the
insulation block may have to be enlarged. See separate burner
installation booklet for further assistance and dimensions.

NOTE

Tighten burner mounting plate screws evenly to slightly
compress rope gasket. Overtightening will cause plate
cracking at corners.

NOTE

Most large burners require support to the floor. See burner
manufacturer's manual for such specifications if needed.

FIGURE 8

Insulating Block

Target Wall

Advertising