Connecting with dial-up modems, Installing the converter, 5 connecting with dial-up modems – Siemens ISOLATED MULTI-DROP SG-6048-01 User Manual

Page 10

Advertising
background image

3

Installing the Converter

Siemens Energy & Automation, Inc.

7

3.5

Connecting with Dial-Up Modems

If the distance between your PC and Isolated Multi-Drop
converter is greater than 3.5 miles, you can connect them
using dial-up modems. To install the Isolated Multi-Drop
converter using dial-up modems, you need these items:

two dial-up modems

one RS-232 serial cable no more than 50 feet in length
(unless your PC’s modem is directly installed in the
computer)

one null modem cable no more than 50 feet in length

a telephone line for each modem

one Isolated Multi-Drop converter mounting kit (if you
want to mount the converter to the switchgear panel)

If you are mounting the Isolated Multi-Drop converter to a
switchgear panel, do that first. (Refer to Appendix B for
mounting dimensions.)
Follow these steps, while referring to Figure 3.4.

1.

Connect one dial-up modem to your PC; use RS-232
serial cable unless your modem is installed directly in
the computer. (If you need help in connecting the
modems and setting their switches, refer to the
modem’s manual.)

2.

Using a null modem cable, connect one dial-up modem
to the RS-232 port on the converter according to

Figure 3.5.

3.

Set the MAN/AUTO switch to AUTO, and use the
BAUD thumbwheel to set the data rate to match that of
the application software and the ACCESS devices on
the network. (In Automatic mode, the converter ignores
the setting of the DCD/RTS switch.)

Figure 3.4 Connecting the Converter with Dial-Up Modems

+

+

+

+

SHLD

SHLD

SHLD

SHLD

-

-

-

-

Port 4

Port 3

Port 2

Port 1

+

+

-

-

Device

#

n

Device

#1

PC

with

Supervisory

Software

RS-232 Cable

50 Ft. Maximum

Isolated Multi-Drop

Converter

To Other

RS-485

Devices

RS-485

Bus

22 AWG Shielded

Twisted-Pair Cable

4000 Ft. Maximum

Null Modem Cable

50 Ft. Maximum

Modem

Modem

IMPORTANT

Use a

null modem cable

between the Isolated
Multi-Drop Converter

and the modem.

Up to 32 devices

Figure 3.5 Pin Assignments for Null Modem Cable

4.

Insert the RS-485 connector(s) into the port(s) on the
front of the converter. (Refer to section 3.1 for
instructions on installing the connector on the RS-485
cable.)

5.

Plug one end of the converter’s power cord into the
120 VAC connection on the converter, and plug the
other end into any 120 VAC grounded power source.

6.

Turn the converter’s power switch on, and verify that
the PWR LED is lit. (Refer to Section 5
“Troubleshooting” if the PWR LED is not lit.)

7.

Start your software.

To

Modem

To

Isolated

Multi-Drop

Converter

Pins 2 and 3

Transposed

1
2
3
4
5
6
7
8

20

1
2
3
4
5
6
7
8

20

*

*

*

Not required

with converter

Advertising