Connecting directly to a pc, Installing the converter, 3 connecting directly to a pc – Siemens ISOLATED MULTI-DROP SG-6048-01 User Manual

Page 8

Advertising
background image

3

Installing the Converter

Siemens Energy & Automation, Inc.

5

3.3

Connecting Directly to a PC

To connect the Isolated Multi-Drop converter directly to a
PC, you need an RS-232 serial cable of not more than 50
feet in length. Make sure the cable is a DCE-DTE cable, not
a null modem cable. The following table lists the minimum
set of required signals and the pin assignments for DB-25 to
DB-25 and DB-9 to DB-25 cable connectors:

To connect the converter to a PC, follow these steps while
refering to Figure 3.3 below:

1.

Connect the plug end of an RS-232 serial cable to
the RS-232 port on the Isolated Multi-Drop converter.

2.

Connect the socket end of the serial cable to an
RS-232 port on your computer.

3.

If you are using application software that requires direct
DCD/RTS control, set the DCD/RTS switch to RTS and
the MAN/AUTO switch to MAN. If you are using
application software that does not require the direct
DCD/RTS control, set the MAN/AUTO switch to AUTO,
and use the BAUD thumbwheel to set the data rate to
match that of the application software and the
ACCESS devices on the network. (In automatic mode,
the converter ignores the setting of the DCD/RTS
switch.)

Figure 3.2 Connecting the Converter Directly to a PC

Table 3.1 RS-232 Pin Assignments

Pin Number

on Connector

Signal Name

2

TxD

3

RxD

4

RTS

7

GND

8

DCD

+

+

+

+

SHLD

SHLD

SHLD

SHLD

-

-

-

-

Port 4

Port 3

Port 2

Port 1

+

+

-

-

Device

#

n

Device

#1

PC

with

Supervisory

Software

RS-232 Cable

50 Ft. Maximum

Isolated Multi-Drop

Converter

To Other

RS-485

Devices

RS-485

Bus

22 AWG Shielded

Twisted-Pair Cable

4000 Ft. Maximum

Up to 32 devices

4.

Insert the RS-485 connector(s) into the port(s) on the
front of the converter. (Refer to section 3.1 for
instructions on installing a connector on the RS-485
cable.)

5.

Connect the supplied power cord to the 120 VAC
connector on the converter, and plug the other end into
any 120 VAC grounded power source.

6.

Turn the converter’s power switch on, and verify that
the PWR LED is lit. (Refer to Section 5
“Troubleshooting” if the PWR LED is not lit.)

7.

Start your software.

Advertising