GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS

Page 11

Horizontal vent systems shall terminate at least 4 feet
(1.3 m) below, 4 feet (1.3 m) horizontally from or 1 foot
(0.23 m) above any door, window or gravity air inlet into
any building. It must not terminate less than 4 feet (1.3
m) horizontally from, and in no case above or below,
unless a 4 feet (1.3 m) horizontal distance is maintained,
from electric meters, gas meters, regulators and relief
equipment and not less than 7 feet (2.3 m) from any
adjacent public walkway. The bottom of the vent
terminal(s) shall be located at least 5 feet (1.5 m) above
the air intake terminal(s). Avoid terminal locations likely
to be affected by winds, snowdrifts, people and pets.

Table 4 - Certified Vent & Intake Terminals

VERTICAL DIRECT VENT SYSTEMS

See Figures 6 & 10. The vent materials used in vertical
positive pressure vent systems must be certified to UL
1738 for installations in the United States, ULS636 for
installations in Canada.

The maximum length for the vertical vent system is
listed in Table 4. Each 90

° elbow is equal to 5 linear

feet (1.5 m) of pipe. To maximize the performance of
single wall sheet metal vent systems locate 90

° elbows

as far from the boiler as possible and from one another.
If any part of a single wall metal vent system passes
through an unheated space it must be insulated with
insulation rated for 400

°F. Structural penetrations must

be made using approved fire-stops.

The vent system must be both gas tight and watertight.
All seams and joints in metal pipes must be joined and
sealed in accordance with the vent system
manufacturer’s instructions.

Vertical vent systems must be terminated with an
approved terminal cap as shown in Figures 6 & 10.

HORIZONTAL VENT
POSITIVE PRESSURE SYSTEMS

See Figure 3. The vent materials used in horizontal
positive pressure vent systems must be certified to UL
1738 for installations in the United States, ULS636 for
installations in Canada.

The maximum vent lengths are listed in Table 3.

Each 90

° elbow is equal to 5 linear feet (1.5 m) of pipe.

To maximize the performance of single wall sheet metal
vent systems locate 90

° elbows as far from the boiler

as possible and from one another. Horizontal vent
systems should be as short and straight as possible.

When horizontal vent runs exceed 5 feet (1.5 m) they
must be supported at 3 foot (0.98 m) intervals with
overhead hangers. The vent system must be pitched
down, toward the vent terminal, 1/4" per foot (21 mm
per meter). If any part of a single wall metal vent system
passes through an unheated space it must be insulated
with insulation rated for 400

°F. Structural penetrations

must be made using approved thimbles.

The vent system must be both gas tight and watertight.
All seams and joints in metal pipes must be joined and
sealed in accordance with the vent system
manufacturer's instructions.

Horizontal vent systems shall terminate at least 4 feet
(1.3 m) below, 4 feet (1.3 m) horizontally from or 1 foot
(0.23 m) above any door, window or gravity air inlet into
any building. It must not terminate less than 4 feet (1.3
m) horizontally from, and in no case above or below,
unless a 4 feet (1.3 m) horizontal distance is maintained,
from electric meters, gas meters, regulators and relief
equipment and not less than 7 feet (2.3 m) from any
adjacent public walkway. The bottom of the vent
terminal(s) shall be located at least 5 feet (1.5 m) above
the air intake terminal(s). Avoid terminal locations likely
to be affected by winds, snowdrifts, people and pets.
Protect building materials and vegetation from
degradation caused by flue gasses.

Table 5- Certified Vent Terminals

Dia. (in.)

3

4

3

4

3

4

3

4

3

4

3

4

3

4

Part No.

300311

300312

300186

300187

300130

300131

300160

300161

7390GC

7490GC

7390TEE

7490TEE

7392GC

7492GC

7314TERM

7414TERM

Company

Protech

Protech

Protech

Protech

Protech

Protech

Protech

Protech

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Description

Tee

Tee

Bird Screen

Bird Screen

45

° Elbow

45

° Elbow

90

° Elbow

90

° Elbow

Mitered

Mitered

Tee

Tee

Screen

Screen

90

° Elbow

90

° Elbow

Dia. (in.)

3

4

3

4

3

4

3

4

3

4

Part No.

300311

300312

300130

300131

300160

300161

7390TEE

7490TEE

7314TERM

7414TERM

Company

Protech

Protech

Protech

Protech

Protech

Protech

Heat-Fab

Heat-Fab

Heat-Fab

Heat-Fab

Description

Tee

Tee

45

° Elbow

45

° Elbow

90

° Elbow

90

° Elbow

Tee

Tee

90

° Elbow

90

° Elbow

Advertising