GS110 DIRECT VENT BOILER INSTALLATION AND OPERATION INSTRUCTIONS

Page 5

When calculating the free area necessary to meet the
make-up air requirements of the enclosure,
consideration must be given to the blockage effects of
louvers, grills and screens.

Screens must have a minimum mesh size of 1/4"
(6.4mm). If the free area through a louver or grill is not
known ducts should be sized per Table 1.

Table 1 - Combustion Air Duct Sizing

Figure 3 - Horizontal Positive Pressure Venting Using Inside Combustion Air (Cat. III)

Figure 4 - Vertical Negative Pressure Masonry Chimney System Using Inside Combustion Air (Cat. I)

Input Btuh

Wooden
Louvers

Input Btuh

Metal

Louvers

Input Btuh

1/4” Wire

Screen Mesh

FreshAir

Duct Size

36,000

64,000

96,000

128,000

108,000

192,000

288,000

384,000

144,000

256,000

384,000

512,000

3” x 12”

8” x 8”

8” x 12”

8-1/2” x 16”