Nexos english 120_layout 1, Installation instructions, Installation manual – Klaxon Nexus 120 DC User Manual

Page 2: Nexus 120 dc sounder & sounder-beacon

Advertising
background image

Installation Manual

Installation

a. The sounder is installed by first mounting the base unit and making the

external wring connections to the base. The head unit then automatically

connects when it is attached to the base.

b. The sounder head is separated from the base by unlocking the four

¼-turn fasteners in the corners of the sounder.
(Recommended screwdriver: Philips No. 2, min 100mm long).

c. Note that the head only fits onto the base one way around. If a beacon

is fitted, care should be taken when mounting the base to ensure that
the beacon will be positioned in the desired orientation after the
sounder is attached

Wiring

The sounder and beacon have separate wiring terminals. Each terminal is
duplicated to enable simple ‘daisy-chain’ connection of multiple units.

Controls

a. Tone Selection

The first and second stage alarm tones are independently set using
6-way dipswitches S1 and S2 respectively. The required settings are
shown in the table overleaf. The third stage alarm tone is pre-set to
complement the selected first stage tone as shown in the table.

b. Volume Control

The sound output of the unit can be reduced by up to 20dBA by
adjusting the potentiometer.

c. Beacon Flash Controls (If fitted)

The flash mode of the beacon can be altered using the 2-way
dipswitch marked

EN

Sounder Positive Supply (10 to 60V DC)
Sounder Negative Supply (0V)
2nd Stage Alarm Control (Connect to 0V to activate)
3rd Stage Alarm Control (Connect to 0V to activate)
Beacon Positive Supply (10 to 60V DC)
Beacon Negative Supply (0V)

Line

Terminal Marking

+
-
S2
S3
+
-

XENON BEACON

LED BEACON

Switch

Off

On

Off

On

1

60 flashes per min 30 flashes per min Single Flash Double Flash

2

Single Flash

Double Flash

Flashing

Static

Technical Specification:

Supply Voltage Range

10-60V DC

Current – Sounder

0.12-0.55A* (Typ. 0.5A @ 24V, Tone 2)

Current –Beacon

Xenon - 250mA Average, 700mA Peak*,

(Where fitted)

LED - 18mA (Flashing) or 65mA (Static)*

Peak Sound Level

110-120 dBA at 1m*

(Typ. 120dBA @ 24V, Tone 2)

Number of Tones

64

Volume Control

20dBA typical

Remote Tone Switching

Provision for 3 alarm stages

(Negative voltage activation)

Operating Temperature

- 25°C to +70°C

Casing

High Impact Polycarbonate/ABS

IP Rating

IP66

Synchronisation

Automatic with Klaxon Nexus and

Sonos Sounders

*depends on selected tone and input voltage. See tone table for details.
EN54-3 certified on tones 1,2,3,6,7 & 13 & > 17V DC only.

The European directive “Waste Electrical and Electronic Equipment” (WEEE)
aims to minimise the impact of electrical and electronic equipment waste on
the environment and human health. To conform with this directive, electrical
equipment marked with this symbol must not be disposed of in European public
disposal systems. European users of electrical equipment must now return
end-of-life equipment for disposal. Further information can be found on the
following website: http://www.recyclethis.info/.