Wiring Inspection

27

10.0 W

IRING

I

NSPECTION

1.

Verify all power connections are tight.

2.

Verify all control wire terminations are tight.

3.

Verify all power wires and connections have proper spacing between exposed surfaces, phase-
to-phase and phase-to-ground.

4.

Verify that all control wires are run in individual, separate, steel conduit.

Table 1

Power Wiring Terminals - Factory Supplied

UPS Module Rating

Connection Type

500 kVA, 6-Pulse Rectifier

All power connections are top or bottom cable entry to busbars on the right
side of module.

500 kVA, 12-Pulse
Rectifier

Busbars for DC input, AC output, Neutral and Ground are provided on the
right side of module, with top or bottom cable entry. Rectifier input is top entry
directly to lugs on top of input circuit breaker.

625-750 kVA, standard
models with standard input

Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input is top entry directly to
lugs on top of input circuit breaker. DC input is top entry to bus bars.

750 kVA/675 kW and other
modules with optional
input busbar kit

Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input and DC input are top
entry to bus bars.

Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this
manual) and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Connect wire to
the lug using tool and procedure specified by the lug manufacturer.

Table 2

Torque Specifications

Nut and Bolt Combinations

Bolt Shaft Size

Grade 2

Standard

Electrical Connections

with Belleville Washers

Lb-in

N-m

Lb-in

N-m

1/4

53

6.0

46

5.2

5/16

107

12

60

6.8

3/8

192

22

95

11

1/2

428

48

256

29

Circuit Breakers With Compression Lugs (For Power Wiring)

Cable Size or Range

Lb-in

N-m

#6 - #4

100

11

#3 - #1

125

14

1/0 - 2/0

150

17

3/0 - 200 MCM

200

23

250 - 400 MCM

250

28

500 - 700 MCM

300

34

Terminal Block Compression Lugs (For Control Wiring)

AWG Wire Size or Range

Lb-in

N-m

#22 - #14

3.5 to 5.3

0.4 to 0.6

Use the values in this table unless the equipment is labeled with a
different torque value.