Table 3 table 310-16, Table 3 – Liebert 600TTM User Manual

Page 34

Advertising
background image

28

Wiring Inspection

Table 3

Table 310-16

Allowable Ampacities of Insulated Conductors Rated 0-2000 Volts, 60° to 90°C (140° to 194°F)

1

Not More than Three Conductors in Raceway or Cable or Earth (Directly Buried), based on Ambient Temperature of 30° (86°F)

Size

Temperature Rating of Conductor. See Table 310-13.

Size

AWG

kcmil

60°C

(140°F)

75°C

(167°F)

90°C

(194°F)

60°C

(140°F)

75°C

(167°F)

90°C

(194°F)

AWG

kcmil

Types

TW*

UF*

Types

FEPW*,

RH, RHW*,

THHW*,

THW*,

THWN*,
XHHW*,

USE*, ZW*

Types

TBS, SA, SIS

FEP*, FEPB*, MI,

RHH*, RHW-2,

THHN*, THHW*,

THW-2, THWN-2,

USE-2, XHH, XHHW*

XHHW-2, ZW-2

Types

TW*

UF*

Types

RH*, RHW*,

THHW*,

THW*,

THWN*,
XHHW*,

USE*

Types

TBS, SA, SIS,

THHN*, THHW*,

THW-2, THWN-2,

RHH*, RHW-2,

USE-2,

XHH, XHHW*,

XHHW-2, ZW-2

Copper

Aluminum or Copper-Clad Aluminum

18
16
14
12
10

8

.......
.......

20†
25†

30
40

.......
.......

20†
25†
35†

50

14
18

25†
30†
40†

55

.......
.......
.......

20†

25
30

.......
.......
.......

20†
30†

40

.......
.......
.......

25†
35†

45

.......
.......
.......

12
10

8

6
4
3
2
1

55
70
85
95

110

65
85

100
115
130

75
95

110
130
150

40
55
65
75
85

50
65
75
90

100

60
75
85

100
115

6
4
3
2
1

1/0
2/0
3/0
4/0

125
145
165
195

150
175
200
230

170
195
225
260

100
115
130
150

120
135
155
180

135
150
175
205

1/0
2/0
3/0
4/0

250
300
350
400
500

215
240
260
280
320

255
285
310
335
380

290
320
350
380
430

170
190
210
225
260

205
230
250
270
310

230
255
280
305
350

250
300
350
400
500

600
700
750
800
900

355
385
400
410
435

420
460
475
490
520

475
520
535
555
585

285
310
320
330
355

340
375
385
395
425

385
420
435
450
480

600
700
750
800
900

1000
1250
1500
1750
2000

455
495
520
545
560

545
590
625
650
665

615
665
705
735
750

375
405
435
455
470

445
485
520
545
560

500
545
585
615
630

1000
1250
1500
1750
2000

Correction Factors

Ambient
Temp °C

For ambient temperatures other than 30°C (86°F), multiply the allowable ampacities shown

above by the appropriate factor shown below.

Ambient
Temp °F

21-25
26-30
31-35
36-40
41-45
46-50
51-55
56-60
61-70
71-80

1.08
1.00

.91
.82
.71
.58
.41

.......
.......
.......

1.05
1.00

.94
.88
.82
.75
.67
.58
.33

.......

1.04
1.00

.96
.91
.87
.82
.76
.71
.58
.41

1.08
1.00

.91
.82
.71
.58
.41

.......
.......
.......

1.05
1.00

.94
.88
.82
.75
.67
.58
.33

.......

1.04
1.00

.96
.91
.87
.82
.76
.71
.58
.41

70-77
78-86
87-95

96-104

105-113
114-122
123-131
132-140
141-158
159-176

* Unless otherwise specifically permitted elsewhere in this Code, the overcurrent protection for conductor types marked with an
asterisk (*) shall not exceed 15 amperes for No. 14, 20 amperes for No. 12, and 30 amperes for No. 10 copper; or 15 amperes for
No.12 and 25 amperes for No. 10 aluminum and copper-clad aluminum after any correction factors for ambient temperature and
number of conductors have been applied.

1

Reprinted with permission from NEC 1999, NFPA 70, the National Electrical Code®, Copyright 1998, National Fire Protection

Association, Quincy, MA 02269. This reprinted material is not the complete and official position of the National Fire Protection
Association, on the referenced subject which is represented only by the standard in its entirety.

Advertising