Minimum clearances, Installation (for qualified installers only), Lk x n m – Lopi DVL Insert EF II User Manual

Page 10: Clearances

Advertising
background image

10

Installation (for qualified installers only)

© Travis Industries

4060111

100-01174

Clearances

Due to the high temperature of the heater, it should be located out of traffic and away from
furniture and draperies.

Side
Wall

Combustible or Non-Combustible Mantel

Combustible Top Facing

Non-Combustible

Facing

Minimum Clearances

k

l

m

n

x

Sidewall to Insert

Side Facing

Top Facing*

Mantel*

Extension onto Hearth

4"

4"

35-1/2"**

35-1/2"**

1-1/4"

l

k

x

n

m

* The non-combustible top facing must extend 1”

above the top of the surround panels.

** Measured from the base of the insert.

Mantel Clearances

The maximum mantel depth is 12”.

NOTE: The combustible area above the facing must not protrude more than 3/4" from the facing.
If it does, it is considered a mantel and must meet the mantel requirements listed in this manual.