Lennox Hearth VIN User Manual

Page 13

Advertising
background image

13

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

A

Flue Opening in the

top of the firebox

A

Restrictor

Restrictor

Installed Over

Flue Opening

Figure 23

Figure 25

Figure 24

Flue Restrictors

The flue restrictor settings shown in Figures 26 and 27 are for typical

installations and may need to be adjusted from standard to take into

account other variables in the installation to achieve proper combustion.

See Flue Restrictor Guidelines on this page to assist you in making a

proper flue restrictor adjustment.

The Vintage™ gas stove uses balanced flue technology to ensure proper

combustion. A flue restrictor may need to be installed depending on the

vent configuration of your stove. The drawings on Page 14 show all the

allowable pipe configurations for the Vintage gas stove. To properly install

the flue restrictor, find your pipe configuration in the drawings on Page

14 and note which restrictor setting is recommended. The flue restric-

tor and two black self-tapping 5/32” allen head screws can be found in

the firebox in a plastic bag. The restrictor should be placed over the flue

opening on the ceiling of the firebox. On the restrictor, two self-tapping

5/32” allen head screws should be installed in either holes 1, 2, 3, or 4

in the restrictor and screwed into the two holes in the firebox ceiling.

See the drawing to the right for the location of hole numbers on the

restrictor. The numbered holes in which the screws are inserted in the

restrictor should correspond to the restrictor position numbers found

on the drawings for your pipe configuration. Restrictor positions are

based on tests run in a laboratory. The optimum restrictor positions may

need to be adjusted slightly depending on the conditions surrounding

the residential installation. Do not adjust restrictors to a point where the

fireplace is sooting.

Notes: The higher the number of the flue restrictor position, the greater

amount of combustion air will be delivered.

Flue Restrictor Adjustment Guidelines

After the flue restrictors have been set to the standard settings as shown

in Figures 26 and 27, the burner flame appearance should be evaluated

to determined if the flue restrictors need to be set to a different position

to adjust for variables in your installation. Light the appliance and allow

it to burn for 20 minutes. See Flame Color and Behavior on Page 18 to

determine if you have a proper burner flame appearance. If the proper

flame appearance cannot be achieved, the flue restrictor may need to be

set to a different position. See the following guidelines to determine if

you need to readjust the flue restrictors.

Before proceeding, confirm the manifold and inlet gas pressure is correct,

primary air shutter is properly adjusted, venting system connections are

secure and not blocked and if you are at a high elevation, ensure unit has

been properly derated:

Symptoms - Lack of Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more open position.

• Flame appears yellow

• Floating Flames (lazy, ill defined, quiet, may roll)

• Sooting

• Pilot becomes yellow and appliance shuts down

Symptoms - Excessive Combustion Air

If the symptoms listed below are present, you may need to adjust the

flue restrictor to a more closed position.

• Low Flame

• Pilot pulls and appliance shuts down

• Pilot flame ghosts

4 3  1

Advertising