Wiring to a Liebert Environmental Unit

The LT300 has two wires for connection to a Liebert environmental

unit.
Note: This sensor should be connected only to a Liebert envi-

ronmental unit.

Figure 1

LT300 to Liebert environmental units

You can wire up to six Liqui-tect 300 sensors to a single alarm point

on a Liebert environmental unit. Sensors should be wired in parallel,

as shown in Figure 2.

Figure 2

Multiple LT300s to Liebert environmental units

Note: When multiple sensors are wired in this manner, you must dis-

connect the sensors one at a time when an alarm occurs to determine

which sensor is in alarm. The alarm will stop when the sensor causing

the alarm is disconnected.

Liebert Deluxe System/3, Challenger,

Himod or Mini-Mate2 (8 ton)

LT300

Liebert Mini-Mate2 (1 to 5 ton)

LT300

Orange wire

Brown wire

Orange wire

Brown wire

Environmental

unit

Environmental

unit

24 (24V)

51, 55 or 56

TB1-1 (24V)

TB1-2 or TB1-3

Liebert environmental unit

LT300

Orange wire

Brown wire

Orange wire

Brown wire

TB1-1 (24V)

TB1-2 or TB1-3