Service Manual

Table 3E Troubleshooting Chart - Noisy System

FAULT

CAUSE

CORRECTIVE ACTION

Noisy

Operation

- Supply gas problem. Natural gas pressures

should be between 4 inches w.c. (1.0 kPa)
and 14 inches w.c. (3.5 kPa). LP gas
pressures should be between 8 inches w.c.
(2.0 kPa) and 14 inches w.c. (3.2 kPa).

• Refer to Section 6 - Gas Connections of the SYNC

Installation and Operation Manual for detailed
information concerning the gas supply.

- Gas/air mixture problem.

• Refer to the Gas Valve Adjustment Procedure on

page 55 of this manual for the proper gas valve setting.
Verify that the vent/air intake lengths do not exceed the
maximum listed in the General Venting section of the
SYNC Installation and Operation Manual.

- Dirty/damaged burner.

• Refer to page 39 in this manual for the burner removal

and inspection procedure. Clean or replace the burner
as necessary.

- Low water flow through the heat exchanger.

• Refer to Section 6 - Hydronic Piping

of the

SYNC Installation and Operation Manual for
minimum flow rates. Verify that the boiler is piped in a
primary/secondary fashion and that the boiler and
system pump are running on a call for heat.

- Air in the piping system.

• Properly purge all air from the piping system.

- Low system water pressure.

• Verify system pressure is a minimum of 12 psi

(82.7 kPa).

No Pump

Operation -

Boiler Pump

System Pump

or

HW Pump

- Blown fuse.

• Replace fuse F5 on the control board, see page 43 of

this manual.

- Faulty pump.

• Replace pump.

- Internal fault on control board.

• Replace main control board.

- Faulty pump relay.

• Replace relay.

Relief Valve

Opening

- System pressure exceeds relief valve

setting.

• Lower the system pressure below the 50 psi

(344.7 kPa) rating of the supplied relief valve or replace
the standard relief valve with a higher rated valve up to
the maximum pressure of the heat exchanger.

• Improperly sized expansion tank.