Troubleshooting – Lochinvar 1.3 User Manual

Page 52

Advertising
background image

Service Manual

Table 3F (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

Air Flow Too

Low

(will require a manual

reset once the condition

has been corrected. Press

the RESET button on the

display to reset.)

Air pressure switch contacts are open.

• Check the wiring connections to switch. Wires should

be connected to the common and normally closed
terminals.

• Vent/air intake lengths exceed the maximum allowed

lengths. Refer to Section 2 - General Venting of the
SYNC Installation and Operation Manual for
proper lengths.

• Check for obstruction or blockage in the vent/air

intake pipes or at terminations.

• Check reference hoses connected to the air pressure

switch for blockage or obstruction.

• Inspect the burner. Reference page 39 of this manual

for removal and cleaning procedures. Replace if
necessary.

• Inspect the heat exchanger. Reference page 40 of

this manual for removal and cleaning procedures.
Replace if necessary.

• Faulty air pressure switch. Replace switch.

Flap valve contacts are in an open position.

• Check the wiring connections to the flap valve switch.

Replace or repair wiring if necessary.

• Check for obstruction in the vent / air intake pipes or

at terminations.

• Verify combustion air blower is operating. Replace if

necessary.

• Replace flap valve switch.

Flap Valve Stuck

Open

Flap valve contacts are in a closed position.

• Check wiring connections to the flap valve switch.

Replace or repair wiring if necessary.

• Check flap valve for obstruction or blockage.

• Replace flap valve switch.

Too Many

Resets - Try Later

Too many manual resets have occurred
during a 15 minute period.

• Wait 15 minutes and try again.

• Turn power off to unit, wait 30 seconds and then turn

power back on.

Voltage Too Low

120 VAC input to the main control board has
dropped below 80 VAC.

• Check 120 VAC supply to the transformer.

• Check wiring connections at the low voltage terminal

strip.

• Check the wire size/length to remote devices.

• Replace the main control board.

Internal Fault

The main control board has detected an
internal fault.

• Replace the main control board.

Writing to

Memos

The main control board has detected an
internal fault.

• Replace the main control board.

52

3

Troubleshooting

Advertising