Installation, Warning – Lincoln AIR VANTAGE IM985 User Manual

Page 14

Advertising
background image

A-6

INSTALLATION

AIR VANTAGE® 500 KUbOTA

A-6

REMOTE CONTROL

The AIR VANTAGE® 500 KUBOTA is equipped with a
6-pin and a 14-pin connector. The 6-pin connector is
for connecting the K857 or K857-1 Remote Control or
for TIG welding, the K870 foot Amptrol or the K963-3
hand Amptrol. When in the CC-STICK, ARC GOUG-
ING or CV-WIRE modes and when a remote control is
connected to the 6-pin Connector, the auto-sensing
circuit automatically switches the OUTPUT control
from control at the welder to remote control.

When in TOUCH START TIG mode and when a
Amptrol is connected to the 6-Pin Connector, the
OUTPUT dial is used to set the maximum current
range of the CURRENT CONTROL of the Amptrol.

When in the DOWNHILL PIPE mode and when a
remote control is connected to the 6-Pin or 14-Pin
connector, the output control is used to set the max-
imum current range of the remote.

EXAMPLE: When the OUTPUT CONTROL on the
welder is set to 200 amps the current range on the
remote control will be 40-200 amps, rather than the
full 40-300 amps. Any current range that is less than
the full range provides finer current resolution for more
fine tuning of the output.

In the CV-WIRE mode, if the feeder being used has a
voltage control when the wire feeder control cable is
connected to the 14-Pin Connector, the auto-sensing
circuit automatically makes OUTPUT CONTROL inac-
tive and the wire feeder voltage control active.
Otherwise, the OUTPUT CONTROL is used to preset
the voltage.

The 14-pin connector is used to directly connect a
wire feeder control cable. In the CV-WIRE mode,
when the control cable is connected to the 14-pin con-
nector, the auto-sensing circuit automatically makes
the Output Control inactive and the wire feeder volt-
age control active.

NOTE: When a wire feeder with a built in welding
voltage control is connected to the 14-pin connec-
tor, do not connect anything to the 6-pin connec-
tor.

--------------------------------------------------------------------------------

AUXILIARY POWER RECEPTACLES

Start the engine and set the “IDLER” control switch to the
“High Idle” mode. Voltage is now correct at the recepta-
cles for auxiliary power. This must be done before a
tripped GFCI module can be reset properly. See the
MAINTENANCE section for more detailed information on
testing and resetting the GFCI module.

The auxiliary power of the AIR VANTAGE® 500 KUBO-
TA consists of two 20 Amp-120 VAC (5-20R) duplex
receptacles with GFCI protection, one 50 Amp 120/240
VAC (14-50R) receptacle and one 50 Amp 240VAC
Three-Phase (15-50R) receptacle.

The auxiliary power capacity is 13,000 watts Peak,
12,000 Watts Continuous of 60 Hz, single phase power.
The auxiliary power capacity rating in watts is equivalent
to volt-amperes at unity power factor. The max permissi-
ble current of the 240 VAC output is 50amps.

The 240 VAC output can be split to provide two separate
120 VAC outputs with a max permissible current of 50
Amps per output to two separate 120 VAC branch cir-
cuits (these circuits cannot be paralleled). Output voltage
is within ± 10% at all loads up to rated capacity.

The Three-Phases auxiliary power capacity is 22,000
watts peak, 20,000 watts continuous. The maximum cur-
rent is 45 amps.

120 V DUPLEX RECEPTACLES AND GFCI MODULES

A GFCI Module protects the two 120V auxiliary power
receptacles.

A GFCI (Ground Fault Circuit Interrupter) is a device to
protect against electric shock should a piece of defective
equipment connected to it develop a ground fault. If this
situation should occur, the GFCI module will trip, remov-
ing voltage from the output of the receptacle. If a GFCI
module is tripped see the MAINTENANCE section for
detailed information on testing and resetting it. A GFCI
module should be properly tested at least once every
month.

The 120 V auxiliary power receptacles should only be
used with three wire grounded type plugs or approved
double insulated tools with two wire plugs. The current
rating of any plug used with the system must be at least
equal to the current capacity of the associated recepta-
cle.

NOTE: The 240 V receptacle has two 120 V circuits, but
are of opposite polarities and cannot be paralleled.

All auxiliary power is protected by circuit breakers. The
120V has 20 Amp circuit breakers for each duplex recep-
tacle. The 120/240V Single Phase and the 240V Three-
Phases have a 50 Amp 3-pole Circuit Breaker that dis-
connects both hot leads and all Three Phases simultane-
ously.

WARNING

Advertising