Lennox Hearth PERFORMER SWS210 User Manual

Page 4

Advertising
background image

4

This manual describes the installation and operation of these non-catalytic

wood heaters. These heaters meet the U.S. Environmental Protection

Agency’s emissions limits for wood heaters sold on or after July 1, 1990.

This heater has been developed, tested and constructed in accordance

with the requirements of UL 1482, ULC S627 and HUD standards and

is listed by OMNI Test Laboratories, Portland, OR. It has been approved

for residential, mobile home and alcove installations.

The appliance is merely one component of a larger system. The other

equally important component is the venting system. This is necessary for

achieving the required flow of combustion air to the fire chamber and for

safely removing unwanted combustion byproducts from the appliance.

If the venting system’s design does not promote these ends, the system

may not function properly. Poorly functioning venting systems may create

TESTING INFORMATION

DRAFT REqUIREMENTS

SELECTING THE PROPER VENTING SYSTEM

Your wood stove is dependent upon a properly functioning chimney for

optimum performance. It is a high efficiency appliance that loses much

less heat up the chimney than older appliances and fireplaces. For this

reason it is important to match the stove to the chimney. The chimney

has two functions:

1. It draws combustion air into the appliance (without air, no fuel will

burn) and

2. It exhausts combustion by-products. Your new appliance is what is

known as a “natural draft” appliance.

The appliance depends solely on the natural draft of the chimney system

to draw combustion air into the unit. Draft is the force that moves air

from the appliance up into the chimney. The amount of draft in your

chimney depends on the length of the chimney, local geography, nearby

obstructions and other factors. Too much draft may cause excessive

temperatures in the appliance (overfiring). Slow or inadequate draft

equals poor combustion and possible smoking problems. The following

are some conditions that may contribute to poor chimney draft:

1. A chimney too large for your appliance.

2. A chimney with not enough height to produce adequate draft.

3. A chimney with excessive height (this may allow exhaust to cool too

much before exiting, which will stall the rate the exhaust exits).

4. Offsets in the venting system are too restrictive (see Chimney Guide-

lines).

Inadequate draft will cause the appliance to leak smoke into the room

through the stove and the chimney connector joints.

Excessive draft may cause an uncontrollable burn or a glowing red stove

or chimney part.

Overfiring Damage - If the heater or chimney connector glows, you are

overfiring. Other symptoms may include: Cracking, warping or burning

out of components, plated accessories may turn color, stove glass may

develop a haze, which will not come off with cleaning.

Overfiring of a stove is a condition where excessive temperatures are

reached, beyond the design capabilities of the appliance. The damage

that occurs from overfiring is not covered under the manufacturer’s

limited warranty.

Also see Troubleshooting on Page 20.

performance problems as well as be a safety hazard. A draft test should

read greater than .04’ W.C. (inches water column) and less than .08”

W.C. As per NFPA-211 standard (see paragraph below), the installer

must take into account all variables within the installation and install the

appliance in such a manner that satisfies the draft requirements of the

appliance. See Chimney Guidelines below to assist you in selecting the

proper venting system for your installation.

American National Standards Institute ANSI/NFPA 211, Standard for

Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances

- See Draft Section: A chimney or vent shall be so designed and con-

structed to develop a flow sufficient to completely remove all flue and

vent gases to the outside atmosphere. The venting system shall satisfy

the draft requirements of the connected appliance in accordance with the

manufacturer’s instructions.

Chimney Guidelines:

• This appliance requires approximately 12 feet minimum of “effective

draw” provided by the venting system. As a rule of thumb, every 90

degree total direction change in the venting will result in a loss of

approximately 5 feet of “effective draw.” Example: If two 45 degree

offsets are used, subtract 5 feet from the actual vertical vent height

to determine your “effective draw.” In this case if you had 14 feet of

vertical vent, the effective draw would only be approximately 9 feet

(14 ft. - 5 ft. = 9 ft.), therefore it may be necessary to add additional

height to the venting system.

• Do not install an offset within the first two feet above the flue outlet

on the appliance.

• In well insulated and weather tight homes, it may be difficult to establish

a good draft up your chimney. The poor draft is caused by a shortage

of air in the house. In this situation an Outside Air Kit may need to

be installed (See Negative Pressure Warning on Page 5 and Outside

Combustion Air on Page 11).

Chimney Height Requirements

The chimney must extend 3’ (.92m) above the level of roof penetration

and a minimum of 2’ (.61m) higher than any roof surface within 10’

(3m) (see below). Check with your local building officials for additional

requirements for your area.

Figure 1

- Chimney Height Requirements

Less than

10' (3 m)

10'

(3 m)

3' (914 mm)

Min.

2’ (610 mm) Min.

(914 mm)

Min.

3'

To pass inspection in nearly any jurisdiction, the chimney must meet both

safety and exhaust flow requirements. The (3’ by) 2’ by 10’ rule applies

to both masonry and factory-built chimneys.

* Ref. USA - National Standard, NFPA 211-latest edition and Canada

National Standard CSA B365-01-latest edition. Vents installed with a

listed cap shall terminate in accordance with the terms of the cap’s

listings.

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

Advertising
This manual is related to the following products: