WARNING: BE ABSOLUTELY SURE THE DISTANCE BETWEEN THE

HEATER AND THE SURFACE OF ANY COMBUSTIBLE CONSTRUC-

TION IS NOT LESS THAN SHOWN IN THE FIGURES ON PAGE 7.

Floor Protection

USA - The floor in front and under the heater must be protected with

noncombustible material. The covering must extend 16” in front of the

door opening of the heater and 8” to either side of the door opening.

Canada - The floor in front and under the heater must be protected with

noncombustible material. The covering must extend 457 mm in front of

the door opening of the heater and 200 mm to either side of the stove

body and 200 mm to the rear or to the wall, whichever is smaller.

USA and Canada - A chimney connector / venting extends horizontally

over the floor, protection must also cover the floor under the connector

/ venting and at least 2” (51 mm) to either side.

Reduced Clearances

Clearances to combustible surfaces can be reduced with the use of listed

double wall connector pipe. See the clearances with double wall pipe on

the following page.

Alcove Clearances:

In alcove installations, only 6” double wall connector pipe can be used

(single wall or single wall pipe with shield is not allowed). Minimum alcove

width between combustible materials is 48” (1219 mm). Maximum alcove

depth is 48” (1219 mm). Minimum alcove height is 72” (1829 mm).

Chimney and Connector

Minimum 6" diameter, minimum 24 MSG black steel connector pipe with

UL103HT listed factory-built chimney suitable for use with solid fuels

or masonry chimney. Horizontal connection not tested, refer to local

building codes for installation. See installation instructions for details.

Restrictions apply! Read instructions before installing.

Residential chimney systems must be from the same brands as listed

for mobile homes but connector pipe may be double wall, single wall or

single wall with shield as listed above.

This appliance may be vented into a code-approved masonry chimney

with flue liner.

Warning: Chimney connector must be in good condition and kept clean.

Do not install damaged parts.

All of the stove connector pipe used must be of the same brand. The

chimney that the stove pipe transitions into may be a different brand.

Other than the transition of the stove pipe into the chimney, do Not mix

different brand vent components. Install all vent components per vent

manufacturer’s instructions.

The chimney connector shall not pass through an attic or roof space,

closet or similar concealed space, or a floor, or ceiling. Where passage

through a wall, or partition of combustible construction is desired, the

installation shall conform to CAN/CSA-B365, Installation Code for Solid-

Fuel-Burning Appliances and Equipment.

There must be an effective vapor barrier at the location where the chimney

or other component penetrates to the exterior of the structure. Follow the

vent manufacturer's detailed instructions.

IMPORTANT NOTE: See Draft Requirements and Selecting a Proper

Venting System on Page 4 to assist you in choosing the proper venting

system for your installation.

Clearance dimensions are to flue collar. If a single wall connector pipe

with shield is used, a 1 inch air space is needed between pipe and shield.

Shield attaches to rear of stove pipe and must run from stove top to ceil-

ing. Pipe shield shall be UL listed.

Components Required For Installations

Legs AND Bottom Heat Shield or Pedestal Base. If optional blower is

NOT used, Rear Heat Shield Block Off Plate shall be installed.

Use all required components specified for this appliance. Do

not substitute.

WARNING: In the event that you remove the blower for any

reason, make sure a cover plate (available from Lennox Hearth

Products) is installed before using the heater. Excessive rear

wall temperatures will result if the stove is burned without the

cover plate. Note: The cover plate is not necessary if a blower

has never been installed because a knock-out will be in place

to act as the cover.

* Other approved chimney brands are Projet, Jakes Evans/GSW, Dura-

vent, Metal Fab, Ameri-Tec, Metalbestos and Industrial Chimney (ICC).

CLEARANCES TO COMBUSTIBLES