2 external protective devices, 3 power cables, External protective devices – Liebert Emerson NX UPS System User Manual

Page 36: Power cables, Input distribution distribution panel

Advertising
background image

UPS Multi-Module Installation

28

Figure 15 Dry contacts, multiple UPS modules with distribution panel

3.2.2 External Protective Devices

Refer to the instructions in 1.0 - Single Module UPS Installation.

3.2.3 Power Cables

The wiring of power cables is similar to that of single module system. The Bypass and the Main input

sources must be referenced to the same neutral potential and input earth leakage monitoring devices,

if installed, must be located upstream of the common neutral sinking point. Refer to the instructions

in 1.0 - Single Module UPS Installation.

NOTE
The length and specification of power cables including the bypass input cables and UPS output

cables should be the same. This facilitates load sharing when operating in bypass mode.

Input Distribution

Distribution Panel

UPS 1

UPS 2

Q1Ext

To Load

Q2Ext QnExt

QByp

QUPS

UPS N

M3 Board

X3

Ext. Maint. Ext. Out

M3 Board

X3

Ext. Maint. Ext. Out

M3 Board

X3

Ext. Maint. Ext. Out

1 2 3 4

1 2 3 4

1 2 3 4