UPS Multi-Module Installation

32

3.4.4 Control Wires

For Liebert NX to NX dual bus configuration, interconnect the optional DBS cable between any DBS

ports of two parallel systems as illustrated in Figure 19.

Figure 19 Connections of a typical dual bus system utilising Load Bus Synch

3.4.5 Extended Dual Bus Synchronization Option (DBS Interface Box)

For Liebert NX to non- NX (whether another Liebert UPS range or not) dual bus configuration, one

DBS interface box shall be mounted on the non- Liebert NX UPS. In this situation, the other UPS sys-

tem is always treated as a master and the following conditions are covered:

• Master and slave are both on inverter
• Master on bypass, slave on inverter

NOTE
Example shown with ring control cables ("8") for DSB applied to two 1+1 paralleled systems.

NOTE
Extended DBS interface box is also used for extending DBS cable length up to

150 meters (490ft) for DBS configuration between two groups of NX UPS systems.