Advanced Controller Programming (Cont.)

Shadow Loop Open Prevention

If the shadow loop is triggered, it always prevents the gate from closing if
the Auto Close Timer activates or a CLOSE command is given while the
gate is at the full open position.

The controller can also be set to prevent the gate from opening if the
shadow loop is triggered while the gate is at the close limit position. This
prevents a swing gate from opening into a vehicle if it’s parked near the
gate on the inside.

Low Power Mode

This function is only used with DC swing gate Model SWD. The
factory default disables the Low Power Mode. When Low Power Mode
is enabled, and AC power fails, the controller will assume Low Power
Mode after 60 seconds of gate inactivity. Low power mode turns off all
accessory power and indicators. Only inputs from the radio receiver,
reverse loop, open loop (optional by programming), fi re department input,
or restoring AC power will wake the Controller from Low Power Mode.
Programming Mode can still be accessed while the Controller is awake
in Low Power Mode.

NOTE: This function will only be displayed in Model SWD operators.

Power Failure Mode

This function is only used with DC swing gate Model SWD. The
factory default is set for Fail Safe, alternately the Controller can be set for
Fail Secure, Open Immediate, or Close Immediate.

• Fail

Safe: If the AC power fails and the battery voltage drops below

approximately 22 Volts, 5 seconds later the operator will cycle open
if not already open. When AC power is restored, or the battery gets
charged by solar panels, the operator will resume normal operation
and auto-close if programmed to do so.

• Fail Secure: If the AC power fails and the battery voltage drops

below approximately 22 Volts, 5 seconds later the operator will
cycle closed if not already closed. When AC power is restored, or
the battery gets charged by solar panels, the operator will resume
normal operation.

NOTE: Fail Safe and Fail Secure are disabled if Stagger Mode is

enabled.

• Open Immediate: If the AC power fails, the operator will cycle

open if not already open and cease operation. When AC power is
restored, the operator will resume normal operation and auto-close
if programmed to do so.

• Close Immediate: If the AC power fails, the operator will cycle

closed if not already closed and cease operation. When AC power is
restored, the operator will resume normal operation.

NOTE: This function will only be displayed in Model SWD operators.

FUNCTION

SET TO FAIL SAFE MODE

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

POWER

FAILURE MODE

"FS"

SET TO FAIL SECURE MODE

DC MODELS

ONLY

SET TO OPEN IMMEDIATE MODE

SET TO CLOSE
IMMEDIATE MODE

FUNCTION

LOW POWER MODE DISABLED

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

LOW POWER

MODE

"LP"

LOW POWER MODE #1
RADIO WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE

DC MODELS

ONLY

LOW POWER MODE #2 - RADIO OR
OPEN LOOP WILL WAKE AND ACTIVATE,
REVERSE LOOP WILL JUST WAKE

THE FIRE DEPARTMENT INPUT

WILL ALWAYS WAKE UP CONTROLLER

FUNCTION

STANDARD OPERATION
SHADOW LOOP INHIBITS CLOSING ONLY

OPTIONS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

SHADOW LOOP

OPEN PREVENTION

"SP"

OPEN INHIBIT ON, SHADOW LOOP INHIBITS
OPENING AND CLOSING