Liebert dcp – Liebert DCP DPN002400 User Manual

Page 4

Advertising
background image

THREE PHASE CONNECTION

Electric service connection terminals

Factory installed disconnect switch

Factory wired to components

on electric panel

EARTH GROUND LUG

Connection terminal for

field supplied earth

grounding wire.

Three phase electric service

not provided by Liebert

ELECTRIC CONDUIT KNOCKOUTS

On top of electric box. Knockout size

2 in (51 mm)

ALARM AND WARNING OUTPUT RELAYS

Field supplied 24V Class 2 wire for

special alarms.

(Not to exceed 1.0A @ 24v each.)

REMOTE UNIT SHUTDOWN

Replace existing jumper between terminals

37 & 38 with normally closed switch having

a minimum 50VA rating. Use field supplied

24V Class 2 wire.
SITE MONITORING CONNECTION

Terminals 77 (-) and 78 (+) are for

connection of a 2 wire, twisted pair,

communication cable (available from

Liebert or others) for optional Sitescan.

(see user's manual).

Monitoring panel

Field supplied disconnect switch may

not be required, check local codes.

Three phase electric service

not provided by Liebert

NOTE: Refer to specification sheet for full load amp. and wire size amp. ratings.

Factory installed unit

disconnect switch

60HZ COMPONETS SHOWN

INTELLISLOTS

Two Liebert Intellislots for optional

OCWEB-LBDS or OC485-LBDS card.

®

®

CANBUS ISOLATOR

REV 0

PAGE 5/6

REV DATE 05/11

Liebert DCP

Liebert DCP

Page 4/5
DPN002400

REV DATE 11/11
REV 0