Liebert DCP Extra Low Voltage field connection points

NOTES:

1. CONTROL WIRING MUST BE CLASS 2 AND INSTALLED IN

ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (NEC).

2. REQUIRES SHIELDED CABLE.

K11COM

COMMON WARNING OUTPUT

K11NO

K11NC

K11

TO REMOTE ALARM

CIRCUIT BY OTHERS

K11

N.O. CONTACT BY OTHERS

FOR INDICATION OF ALARM, WIRE

N.O. CONTACTS FROM REMOTE

ALARM DEVICE AS SHOWN.

24

50

INPUT: REMOTE ALARM DEVICE

N.O. CONTACTS REQUIRED

54

24

ALARM WHEN CLOSED.

INPUT: FAN BREAKER STATUS

N.O. CONTACTS REQUIRED

51

24

ALARM WHEN CLOSED.

INPUT: CONDENSATION

DETECTION

FOR SHUTDOWN OF CONTROL

CIRCUIT, REMOVE JUMPER

BETWEEN TERMINALS 37 & 38

AND REPLACE WITH N.C. CONTACT

38

37

INPUT: REMOTE SHUTDOWN

N.C. CONTACTS BY OTHERS

K3COM

COMMON ALARM OUTPUT

K3NO

K3NC

K3

TO REMOTE ALARM

CIRCUIT BY OTHERS

FOR CONTACTS INDICATING AN

ALARM CONDITION.

(MAX) 1.0AMP @ 24V

K3

BK

78

77

(-)

R or W

FOR DIGITAL COMMUNICATIONS

WITH LIEBERT SITE MONITORS

ONLY. CONNECT 2 WIRE TWISTED

PAIR TO 77 & 78. ALSO SEE SITE

MONITOR INSTALLATION MANUAL.

LIEBERT SITE MONITOR

(+)

FOR CONTACTS INDICATING AN

ALARM CONDITION.

(MAX) 1.0AMP @ 24V

FACTORY WIRED

TEMPERATURE SENSOR.

1

1

2

TO REMOTE T/H SENSOR A

P67

DO NOT

USE

UNIT DISPLAY (REAR VIEW)

TO OPTIONAL

EXTERNAL

CONNECTIONS

TO REMOTE T/H SENSOR B

P64

P67

P66

TO P64 ON ICOM CONTROL BOARD

RED ETHERNET CABLE

TO P66 ON ICOM CONTROL BOARD

TERMINATION PLUG

REV 0

PAGE 6/6

REV DATE 05/11

Liebert DCP

Liebert DCP

Page 5/5
DPN002400

REV DATE 11/11
REV 0