Issue 1

May 1999

Customer Responsibilities

B-3

Cable Connections

Table B-2.

Air Purity Requirements

Cable Connections

The customer is responsible for providing several connections from the
customer’s facilities to the DEFINITY AUDIX system. These connections
divide maintenance responsibilities between Lucent Technologies and
the customer:

All customers must provide a Cmentral Office (CO) line or a Direct
Inward Dialing (DID) line to connect the modem to an external
telephone network for remote maintenance.

1

All customers must provide a power source for the external
modem.

1

Customers using I

NTUITY

Message Manager must provide a

10BaseT to connect the DEFINITY AUDIX system to the
customer’s local area network (LAN).

Figure B-1

shows the connections customers must provide for the

external modem.

Contaminant

Average concentration

Total particulate matter, including the following:

185.00 microgram/m

3

Dust

Lint

Carbon particles

Paper fiber

Metal fragments

Nitrate in particulate matter

12.00 microgram/m

3

Corrosive gases

Total hydrocarbons equivalent to methane

10.00 ppm

Sulphur dioxide

0.20 ppm

Oxides of nitrogen

0.30 ppm

Total oxidants equivalent to ozone

0.05 ppm

Hydrogen sulfide

0.10 ppm

1.

Customers outside the U.S. must provide an external modem.