Wiring

Radar Tank Gauge

28

Installation and Operations Manual

4.2

Connecting the measuring unit

Terminal compartment

The housing comes with a separate terminal compartment.

Load HART

Minimum load for Hart communication: 250 Ω

Cable entry

Cable gland: M20x1.5 or Pg13.5

Cable entry: G ½ or ½ NPT

Supply voltage

Direct current voltage: 16…36 VDC

.

Power consumption

Max. 330 mW at 16 V, max. 500 mW at 24 V, max. 600 mW at 30 V.

Current consumption

Max. 21 mA (50 mA inrush current).

Power supply

For stand alone operation recommended via e.g. Varec RN 221N.

mm accuracy

For measurements with mm accuracy the measured variable must be transmitted
using HART protocol to ensure the necessary resolution.

Communication

Terminal voltage

minimal

maximal

Power supply

Standard

U

(20 mA) =

16 V

36 V

Ex

U (20 mA) =

16 V

30 V

Signal

Ex

U (4 mA) =

11,5 V

30 V

U (20 mA) =

11,5 V

30 V