Radar Tank Gauge

62

Installation and Operations Manual

manual

The value pairs in the dip table can be read and written. You can enter the measured

value and the dip value.

–uncorrected measured value:

This is the measured value supplied by the instrument, NOT corrected by the dip

table. The choice of measured value, level or remaining fill height is dependent on

the instrument setting.

–Dip value:

This is the level or distance to flange respectively, given by the hand dip. This value

should be used to correct the measured value.

The "manual mode" of the dip table can be used to enter collected data after a series

of data pairs taken at different tank levels.

Note!

The bigger the distance between the different levels while taking hand dips, the more

accurate the linearization of the dip table will be.

semi-automatic

The value pairs in the dip table can be read. You can enter the dip value only. When there

are new value pairs, the current level or distance is accepted as the measured value.

table on

The dip table is switched on.

table off

The dip table is switched off.

clear table

The complete dip table is deleted. The table is switched off. The number of free table

entries is set to the maximum value (= 32).

View

The value pairs in the dip table can only be read. You can still select this menu option,

even if there is no dip table available. In this case, the number of free table entries is at

maximum value (= 32).

Function "dip table" (034)

This function edits measured variable. The number behind the entry "remain" indicates

the current number of remaining free value pairs. The maximum number of value pairs

is 32; after each entry, the remaining number is decremented.

Note!

The uncorrected measured value is displayed in the "dip table" (034) function. This may

differ considerably from the measured values when a dip table is activated.

Function "dip table" (035)

This function edits the dip value.