PLANNING YOUR INSTALLATION

PAGE 5

FLOOR PROTECTION
This appliance requires non-combustible floor protec-
tion for ember protection. If the floor protection is to be
stone, tile, brick, etc., it must be mortared or grouted to
form a continuous non-combustible surface. If a chim-
ney connector extends horizontally over the floor, pro-
tection must cover the floor under the connector and at
least 2" (51 mm) to either side.

The floor protection must extend completely beneath
the stove and to the front, sides, and rear as indicated:

USA REQUIREMENTS
16” (406 mm) min. to the front of the fuel door glass
8” (203 mm) min. beyond the sides of the fuel door

opening

0” (0 mm) min. to the back of the stove body

CANADA REQUIREMENTS
18” (457 mm) min. to the front of the fuel door glass
8” (203 mm) min. beyond the sides of the stove body
8” (203 mm) min. to the back of the stove body

STANDARD PARALLEL HEARTH PAD SHOWN



8” (203 mm)

Canada

8” (203 mm)

USA

8” (203 mm)

USA

8” (203 mm)

Canada

0” - USA

8” – Can.

18” (457 mm) – Can-

ada

16” (406 mm) USA

DOOR

STOVE TOP