Installation & Operation Manual

Figure 5-3 Pump Configuration

5

Hydronic piping

(continued)

27

Hot Water Generator pump sizing

The SYNC has two (2) heat exchanger modules that require two (2) individual pumps for proper installation in the boiler loop
and an additional two (2) pumps for the Hot Water Generator loop.

Hot Water Pump Head Loss = Ft. of Head for Module 1 (at required flow) + Ft. of Head for the Hot Water Generator (at 2 X the
flow of Module 1)

Example:

Boiler: SB1500
A

ΔT of 30° requires a flow through each module of 51 GPM. The module head loss is 18 ft. of head (see Table 5A).

Coupled with a Lochinvar Hot Water Generator with a 8-42 (diameter-length) tube bundle the calculated pressure drop is
1.2 Ft. of Head at 102 GPM.

Hot Water Pump Head Loss = 18 Ft/Hd (51 GPM) + 1.2 Ft/Hd (102 GPM) = 19.2 Ft/Hd

A pump will need to be selected to flow 51 GPM with a head loss of 19.2 Ft/Hd.

Figure 5-2 Boiler Schematic

MODULE 1
HOT WATER PUMP

MODULE 2

HOT WATER PUMP

MODULE 2

BOILER PUMP

MODULE 1

BOILER PUMP

102 GPM

51 GPM

102 GPM

51 GPM

TO SYSTEM

FROM SYSTEM

HOT WATER

GENERATOR

AIR COVER

OK

TO BOILER

INLETS

FROM SYSTEM

NO

TO BOILER

INLETS

FROM SYSTEM