Chapter 2. SPECIFICATIONS


2 - 11

2.4.3

Simultaneous Voltage and Current Input Characteristics

1) G3F-AD3A, G4F-AD3A
For simultaneous voltage and current input, the input conversion switch of each channel is set to corresponding

voltage and current range.

Ex) Voltage input range: 0 to 3 Current input range: 4 to 7










- Digital output value for analog input is shown as follows..

Analog input

0~10V

-0.12

0

2.5

5

7.5

10

10.12

Voltage
(V)

1~ 5V

0.952

1

2

3

4

5

5.048

Current

(mA)

4 ~ 20 mA

3.808

4

8

12

16

20

20.192

Digital output value

-48

0

1000

2000

3000

4000

4047




2) G6F-AD2A

For simultaneous use of voltage and current input, the available input voltage rage is 0 ~ 5VDC only.

Digital output value for analog input is shown as follows..

Analog input

Voltage DC1~ 5V

0.952

1

2

3

4

5

5.048

Current DC4 ~ 20mA

3.808

4

8

12

16

20

20.192

-48

0

1000

2000

3000

4000

4047

Digital output value

-2048

-2000

-1000

0

1000

2000

2047

Ex) channel for voltage : 0, channel for current : 1

Wiring Example

Input Rage Selection Switch

Voltage Input(Channel “0”)

Current Input(Channel ”1”)


Input selection switch

On


1 2 3 4 5 6 7 8

- On : Current
- Off : Voltage

(

)

CH 0 1 2 3 4 5 6 7

1

2

3

J1

J2

V+

I+

COM

+

Analog Input

V+

I+

COM

+

Analog Input