2) g6f-ad2a – LG G4F-AD3A User Manual

Page 32

Advertising
background image

Chapter 4. FUNCTION BLOCK

4 - 5

4.2.3 Module Reading - Single Type

1) G3F-AD3A, G4F-AD3A

Single type of function block for reading the module is performed for only one channel and the specified
channel is used to read output variable of data displayed from A/D conversion digital value.

Function

block

I/O

Variable

Data

type

Descriptions

REQ

BOOL

Function Block Execution Request Area

- The execution of function block reading is requested in this area.

- If the status to be connected with this area is satisfied on the program operation and

input condition changes from low(0) to high(1), function block initialization for the

module is executed.

BASE

USINT

Base Module Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0 ~ 3

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

Input

CH

USINT

Available Channel Specification Area

- Enabled channels are specified to 1 and disabled channels are specified to 0.

DONE

BOOL

Function Block Execution Complete Area

- When function block reading is executed with no error, 1 is written and until next

execution, 1 is continuing. When error occurs, 0 is written and operation come to stop.

STAT

USINT

Error Code Display Area

- When error occurred during function block initialization, the error code number is

written.


output

DATA

INT

A/D Conversion Value Output Area

Output data range : -47 ~ 4048

2) G6F-AD2A

Single type of function block for reading the module is performed for only one channel and the specified
channel is used to read output variable of data displayed from A/D conversion digital value.

Function

block

I/O

Variable

Data

type

Descriptions

REQ

BOOL

Function Block Execution Request Area

- The execution of function block reading is requested in this area.

- If input condition is changed from low(0) to high(1), function block initialization for

the module is executed.

BASE

USINT

Base Module Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

Input

CH

BOOL[4]

Available Channel Specification Area

Setting range : 0 ~ 3

DONE

BOOL

Function Block Execution Complete Area

- When function block reading is executed with no error, 1 is written and 1 is kept

until next execution. When error occurs, 0 is written and operation come to stop

STAT

USINT

Error Code Display Area

- When error occurs during function block reading, the error code number is written.
- Error code is referred to Manual 4.3.

Output

DATA

INT[4]

A/D Conversion Value Output Area

- Output data range : -48 ~ 4047 or –2048 ~ 2047


REQ

BASE

SLOT

CH

AD3RD

STAT

DATA

DONE

REQ

BASE

SLOT

CH

DATA

AD2RD

STAT

DONE

Advertising
This manual is related to the following products: