INSTALLATION

GX 271 Chopper

A-8

Connection of GX-271 to premises wiring must be done by a licensed electrician and must comply with
the National Electrical Code and all other applicable electrical codes.

230 Volt

60 Hz.

3-Wire

Service

POWER

COMPANY

METER

230 VOLT

115 VOLT

115 VOLT

LOAD

N

NEUTRAL
BUS

GROUND

PREMISES

DISCONNECT AND

SERVICE

OVERCURRENT

PROTECTION

GND

N

NOTE: No. 8 COPPER CONDUCTOR CABLE SEE

NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

230 VOLT

GROUNDED CONDUCTOR

35 AMP

230 VOLT

DOUBLE

POLE

CIRCUIT

BREAKER

DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

50 AMP, 115/230

VOLT PLUG

NEMA TYPE 14-50

50 AMP, 115/230 VOLT

RECEPTACLE

Figure A.1

CONNECTION OF GX-271 TO PREMISES WIRING

Table A.1

Extension Cord Length Recommendations

WARNING

Current

Voltage

Load

Maximum Allowable Cord Length in ft (m) for Conductor Size (AWG)

(Amps)

(Volts)

(Watts)

14 AWG

12 AWG

10 AWG

8 AWG

6 AWG

4 AWG

15

120

1800

30

(9)

40

(12)

75

(23)

125

(38)

175

(53)

300

(91)

15

240

3600

60

(18)

75

(23)

150

(46)

225

(69)

350

(107)

600

(183)

20

240

4800

60

(18)

100

(30)

175

(53)

275

(84)

450

(137)

25

240

600

90

(27)

150

(46)

225

(69)

250

(76)

30

240

7200

75

(23)

120

(37)

175

(53)

300

(91)

35

240

8400

100

(30)

150

(46)

250

(76)